7.3 Precautions for Using Annunciator (F) in Redundant System
7
PROGRAMMING CAUTIONS
7.3 Precautions for Using Annunciator (F) in Redundant System
The annunciator defaults to no tracking.
In the tracking setting of the Redundant parameter dialog box, the annunciator can be set
to within the tracking range.
Table7.6 provides an operation example of the control system and standby system CPU
modules when the annunciator is set to within the tracking range and the annunciator
(F10) is turned ON in the control system CPU module.
If system switching occurs when the annunciator (F10) turns on in the control system CPU
module, whether the annunciator is on or not cannot be checked by the USER LED since
the USER LED is off in the new control system CPU module.
Table7.6 Operations of Control System and Standby System CPU Modules When F10 Is Turned ON in Control System CPU Module
Item
Control System CPU Module
Standby System CPU Module
F10
Annunciator
ON
ON
SM62
Annunciator detection
ON
OFF
SD62
Annunciator No.
The annunciator No. turned on is stored.
No change
SD63
No. of annunciators
Number of annunciators turned on is
stored.
No change
SD64
to
SD79
Annunciator detection
number table
The annunciator No. turned on is stored.
No change
"USER" LED
On
Off
Diagram 7.12 Operation of USER LED When Annunciator (F10) Turns On
Tracking cable
System switching
Tracking cable
System A/Control system
Standby system
System A/Control system
System B/Standby system
Annunciator tracking
LED status
USER
Program
M0
0
SET
F10
LED status
USER
Program
M0
0
SET
F10
LED status
USER
Program
M0
0
SET
F10
LED status
USER
Program
M0
0
SET
F10
System B/Control system
Standby system