8.1 Communication Between CPU Module and Intelligent Function Modules
8.1.1 Initial setting and auto refresh setting by GX Configurator
8
COMMUNICATION WITH INTELLIGENT FUNCTION
MODULE
(3) Restrictions on the number of parameter settings
There are restrictions on the number of parameter (initial setting or auto refresh
setting) set by GX Configurator.
When mounting the multiple intelligent function modules, make the setting of the GX
Configurator so that the total number of parameter setting of intelligent function
modules does not exceed the maximum number of parameter settings shown in
Table8.2.
<<Concept of number of parameter settings>>
(4) Precautions
The AnS/A series corresponding special function module does not support the
settings made by GX Configurator.
Remark
For the details of GX Configurator, refer to the manual of the intelligent function
module being used.
Table8.2 Number of parameter settings that can be set by GX Configurator
CPU module
Number of parameter settings
Initial setting
Auto refresh setting
Q00JCPU, Q00CPU, Q01CPU, Q02CPU, Q02HCPU,
Q06HCPU, Q12HCPU, Q25HCPU, Q02PHCPU,
Q06PHCPU, Q12PHCPU, Q25PHCPU,
Q12PRHCPU, Q25PRHCPU, MELSECNET/H remote
I/O station
512
256
Q02UCPU
2048
1024
Q03UDCPU, Q04UDHCPU, Q06UDHCPU,
Q13UDHCPU, Q26UDHCPU, Q03UDECPU,
Q04UDEHCPU, Q06UDEHCPU, Q13UDEHCPU,
Q26UDEHCPU
4096
2048
Figure 8.3 Concept of number of parameter settings
This one line is counted as
one setting. Blanks are not counted.
All the setting items in this setting
screen are added,
which is summed up with the
number of other intelligent function
modules.