12. High pressure sensor (63HS)disassembly procedures:
(1) Remove the side panel (Refer to 1).
(2) Remove the electrical box (Refer to 4).
(3) Remove the high pressure sensor wire.
(4) Remove the welded portion of high pressure sensor.
(5) Remove the mounting screw fastening the high
pressure sensor mounting plate (1 pc : 4
o
10).
(6) Remove the high pressure sensor mounting screws
(2 pcs : 4
o
10).
Photo 12
Photo 13
13. Capillary tube disassembly procedures:
(1) Remove the side panel (Refer to 1).
(2) Remove the top panel (Refer to 1).
(3) Remove the electrical box (Refer to 4).
(4) Remove the field piping from the unit (liquid side).
(5) Remove the welded portions of the lower coil inlet
and expansion valve mounting part.
Welding part
Separator
fixing screw
High pressure
sensor mount
High pressure
sensor
Expansion
valve
Capillary tube2
Capillary tube3