background image

11

D

F

E

I

NL

P

GR

RU

TR

CZ

SV

SL

HG

PO

GB

Caution:

Only use refrigerant R410A.

- The use of other refrigerants such as R22 or R407C, which contains chlorine,

will deteriorate the refrigerating machine oil or cause the compressor to malfunc-
tion.

2

Evacuation

Evacuate with the valve of the outdoor unit closed and evacuate both the con-
nection piping and the indoor unit from the service port provided on the valve
of the outdoor unit using a vacuum pump. (Always evacuate from the service
port of both liquid pipe and gas pipe.) After the vacuum reaches 650 Pa [abs],
continue evacuation for at least one hour or more. Then, stop the vacuum
pump and leave it for 1 hour. Ensure the degree of vacuum has not increased.

(If the degree of vacuum increase is larger than 130 Pa, water might have
entered. Apply pressure to dry nitrogen gas up to 0.05 MPa and vacuum
again.)

 Finally, seal in with the liquid refrigerant through the liquid pipe, and

adjust the gas piping to obtain an appropriate amount of the refrigerant during
operation.
* Never perform air purging using refrigerant.

[Fig. 9.3.2] (P.4)

A

System analyzer

B

Low knob

C

Hi knob

D

Valve

E

Liquid pipe

F

Gas pipe

G

Service port

H

Three-way joint

I

Valve

J

Valve

K

R410A cylinder

L

Scale

M

Vacuum pump

N

To indoor unit

O

Outdoor unit

Note:

Always add an appropriate amount of refrigerant. Also always charge the
system with liquid refrigerant.

Use a gauge manifold, charging hose, and other parts for the refrigerant
indicated on the unit.

Use a graviometer. (One that can measure down to 0.1 kg.)

Use a vacuum pump with a reverse flow check valve.
(Recommended vacuum gauge: ROBINAIR 14830A Thermistor Vacuum
Gauge)
Also use a vacuum gauge that reaches 65 Pa [abs] or below after operat-
ing for five minutes.

3

Refrigerant Charging

Since the refrigerant used with the unit is nonazerotropic, it must be charged in
the liquid state. Consequently, when charging the unit with refrigerant from a
cylinder, if the cylinder does not have a syphon pipe, charge the liquid refriger-
ant by turning the cylinder upside-down as shown in Fig. 9.3.3. If the cylinder
has a syphon pipe like that shown in the picture on the right, the liquid refriger-
ant can be charged with the cylinder standing upright. Therefore, give careful
attention to the cylinder specifications. If the unit should be charged with gas
refrigerant, replace all the refrigerant with new refrigerant. Do not use the re-
frigerant remaining in the cylinder.

[Fig. 9.3.3] (P.4)

A

Syphon pipe

B

In case of the R410A cylinder having  no syphon pipe.

Heat

insulation

material A

Outer

covering B

9.4. Thermal insulation of refrigerant piping

Be sure to add insulation work to refrigerant piping by covering liquid pipe and gas
pipe separately with enough thickness heat-resistant polyethylene, so that no gap
is observed in the joint between indoor unit and insulating material, and insulating
materials themselves. When insulation work is insufficient, there is a possibility of
condensation drip, etc. Pay special attention to insulation work in the ceiling ple-
num.

[Fig. 9.4.1] (P.4)

A

Steel wire

B

Piping

C

Asphaltic oily mastic or asphalt

D

Heat insulation material A

E

Outer covering B

Glass fiber + Steel wire

Ad Heat - resistant polyethylene foam + Adhesive tape

Indoor

Vinyl tape

Floor exposed

Water-proof hemp cloth + Bronze asphalt

Outdoor

Water-proof hemp cloth + Zinc plate + Oily paint

Note:

When using polyethylene cover as covering material, asphalt roofing shall
not be required.

No heat insulation must be provided for electric wires.

[Fig. 9.4.2] (P.4)

A

Liquid pipe

B

Gas pipe

C

Electric wire

D

Finishing tape

E

Insulator

[Fig. 9.4.3] (P.4)

Penetrations

[Fig. 9.4.4] (P.4)

<A> Inner wall (concealed)

<B> Outer wall

<C> Outer wall (exposed)

<D> Floor (waterproofing)

<E> Roof pipe shaft

<F> Penetrating portion on fire limit and boundary wall

A

Sleeve

B

Heat insulating material

C

Lagging

D

Caulking material

E

Band

F

Waterproofing layer

G

Sleeve with edge

H

Lagging material

I

Mortar or other incombustible caulking

J

Incombustible heat insulation material

When filling a gap with mortar, cover the penetration part with steel plate so that
the insulation material will not be caved in. For this part, use incombustible mate-
rials for both insulation and covering. (Vinyl covering should not be used.)

Insulation materials for the pipes to be added on site must meet the following
specifications:

*

Installation of pipes in a high-temperature high-humidity environment, such as
the top floor of a building, may require the use of insulation materials thicker
than the ones specified in the chart above.

*

When certain specifications presented by the client must be met, ensure that
they also meet the specifications on the chart above.

Caution:

Make sure to seal-off and excess space around areas where the wires and
refrigerant pipes enter the unit.

Small animals, rainwater, or snow entering through the openings may
cause damage to the device.

9.3. Airtight test, evacuation, and refrigerant

charging

1

Airtight test

Perform with the valve of the outdoor unit closed, and pressurize the connec-
tion piping and the indoor unit from the service port provided on the valve of
the outdoor unit. (Always pressurize from both the liquid pipe and the gas pipe
service ports.)

Restriction

• If a flammable gas or air (oxygen) is used as the pressurization

gas, it may catch fire or explode.

Airtight test procedure

(1) After pressurizing to the design pressure (4.15 MPa) using nitrogen gas, allow it to stand for

about one day. If the pressure does not drop, airtightness is good.

However, if the pressure drops, since the leaking point is unknown, the following bubble test

may also be performed.

(2) After the pressurization described above, spray the flare connection parts, brazed parts, and

other parts that may leak with a bubbling agent (Kyuboflex, etc.) and visually check for bubbles.

(3) After the airtight test, wipe off the bubbling agent.

[Fig. 9.3.1] (P.4)

A

Nitrogen gas

B

To indoor unit

C

System analyzer

D

Low knob

E

Hi knob

F

Valve

G

Liquid pipe

H

Gas pipe

I

Outdoor unit

J

Service port

Observe the following restrictions when conducting an air tightness test to prevent
negative effects on the refrigerating machine oil. Also, with nonazeotropic refriger-
ant (R410A), gas leakage causes the composition to change and affects perform-
ance. Therefore, perform the airtightness test cautiously.

Thickness
Temperature Resistance

Pipe size

ø6.35 to 25.4 mm

10 mm min.

ø28.58 to 41.28 mm

15 mm min.

100°C min.

Summary of Contents for PUHZ-RP250YHM-A

Page 1: ...OUTDOOR UNIT PUHZ RP250YHM A For use with R410A INSTALLATION MANUAL For safe and correct use please read this installation manual thoroughly before installing the air conditioner unit GB...

Page 2: ...Unit height C Back D Air outlet guide Procured at the site A Front B Must be open C Wall height H 15 15 450 300 A A 100 450 50 50 A A A B B 500 H h h H 240 45 A D C 50 C 1000 30 450 300 C B B C A 100...

Page 3: ...When closing Turn the shaft clockwise with a hexagonal wrench Turn around the shaft until it stops C Flare nut Coat the flare contact surface with refrigerating machine oil small amount of ester oil...

Page 4: ...C A B D E Fig 9 4 1 B A D C E E E D A B A B A Inner wall concealed A B D C B Outer wall A Steel wire B Piping C Asphaltic oily mastic or asphalt D Heat insulation material A E Outer covering B A Liqui...

Page 5: ...2 L3 N Terminal block for indoor outdoor transmission line TB3 Power supply terminal block TB1 Control box A B Fig 10 2 1 10 3 10 2 Fig 10 2 2 A B C Fig 10 3 1 10 A Power source B Transmission line C...

Page 6: ...When installing and moving the air conditioner to another site do not charge it with a refrigerant different from the refrigerant specified on the unit If a different refrigerant or air is mixed with...

Page 7: ...hazardous sulphur oxides dust dirt shaving particles oils moisture or any other contami nant Contaminants on the inside of the refrigerant piping may cause the refriger ant residual oil to deteriorate...

Page 8: ...eight 4 If there are obstacles at the upper part of the unit 2 In case of collective installation Fig 5 0 2 P 2 A Front B Must be open C Wall height H When multiple units are installed adjacent to eac...

Page 9: ...9 05 for R410A air conditioner choice of pipe type is up to you 8 Never use refrigerant to perform an air purge Always evacuate using a vacuum pump 9 Always insulate the piping properly Insufficient i...

Page 10: ...ming Open fully after these operations are completed When opening Turn the shaft counterclockwise with a hexagonal wrench Turn around the shaft until it stops When closing Turn the shaft clockwise wit...

Page 11: ...t D Heat insulation material A E Outer covering B Glass fiber Steel wire Adhesive Heat resistant polyethylene foam Adhesive tape Indoor Vinyl tape Floor exposed Water proof hemp cloth Bronze asphalt O...

Page 12: ...e outdoor units to TB3 M1 M2 Terminal of only one of the outdoor units 3 In the case of indoor outdoor transmission line connect the shield ground to the grounding terminal 4 Fix the connected wires s...

Page 13: ...rted up Operate remote controller again after H0 or PLEASE WAIT disappear This is a switching sound of the refrigerant circuit and does not imply a problem Unstable flow of the refrigerant emits a sou...

Page 14: ...GB E F I NL E P GR RU TR...

Page 15: ...GB E F NL E P GR RU TR...

Page 16: ...e number on this manual before handing it to the customer This product is designed and intended for use in the residential commercial and light industrial environment The product at hand is based on t...

Reviews: