background image

9

<Returning to the Main menu>

F1

F2

F3

F4

Main

Main display:

Cursor

Page

Main menu

Vane·Louver·Vent. (Lossnay)
High power
Timer
Weekly timer
OU silent mode

Note:

 

 

During swing operation, the directional indication on the screen 
does not change in sync with the directional vanes on the unit.

  Available directions depend on the type of unit connected.

 

  In the following cases, the actual air direction will differ from the 

direction indicated on the remote controller display.

 

1. While the display is in “STAND BY” or “DEFROST” states.

 

2.  Immediately after starting heat mode (while the system is wait-

ing for the mode change to take effect).

 

3.  In heat mode, when room temperature is higher than the tem-

perature setting.

<Display of unsupported functions>

The message at left will appear if 
the user selects a function not sup-
ported by the corresponding indoor 
unit model.

F1

F2

F3

F4

Title

Not available

Unsupported function

Return:

3.5.2 Vane·Vent. (Lossnay)

<Accessing the menu>

F1

F2

F3

F4

Main

Main display:

Cursor

Page

Main menu

Vane·Louver·Vent. (Lossnay)
High power
Timer
Weekly timer
OU silent mode

Select "Vane·Louver·Vent. (Loss-
nay)" from the Main menu (refer to 
page 8), and press the [SELECT]  
button.

<Vane setting>

F1

F2

F3

F4

Fri

Swing

Off

Off

Louver

Vent.

Vane

Cool

Room

Auto

Set temp.

Mode

Temp.

Fan

Fri

<Vent. setting>

F1

F2

F3

F4

Fri

Low

Vent.

3. Operation 

Press the [RETURN] button to go 
back to the Main menu.

Press the [F1] or [F2] button to go 
through the vane setting options: 
"Auto", "Step 1", "Step 2", "Step 3", 
"Step 4", "Step 5" and "Swing". 
Select the desired setting.

Auto

Auto

Swing

Step 1

Step 2

Step 4

Step 3

Swing

Step 5

Select "Swing" to move the vanes 
up and down automatically.
When set to "Step 1" through "Step 
5", the vane will be 

fi

 xed at the se-

lected angle.

 • 

 under the vane setting icon

  This icon will appear when the 

vane is set to "Step 2" to "Step 5" 
and the fan operates at "Mid 1" 
to "Low" speed during cooling or 
dry operation (depends on the 
model).

  The icon will go off in an hour, and 

the vane setting will automatically 
change.

Press the [F3] button to go through 
the ventilation setting options in the 
order of "Off", "Low", and "High".
* Settable only when LOSSNAY 

unit is connected.

Off

Low

High

Off

Low

High

•  The fan on some models of in-

door units may be interlocked 
with certain models of ventilation 
units.

 

PCA-RP•HAQ

Move the vane to the desired position. (The position of the vane can be 
changed within the range from 10

° 

up to 45

°

 down.)

*  If the vane is in the downward position during cooling or dry mode, 

condensation may form and drip from the air outlet. If this occurs, ad-
just the air

fl

 ow direction.

*  If the cool air

fl

 ow blows directly onto a 

fl

 ame, cooking table, or food, 

and affects the cooking, adjust the air

fl

 ow direction.

<[Manual] To Change the Airfl ow's Left/Right Direction>

*  The louver button cannot be used.

   Model PKA-RP·KA

•  Stop the unit operation, hold the lever of the louver, and adjust to 

the desired direction.

*  Do not set to the inside direction when the unit is in the cooling or 

drying mode because there is a risk of condensation and water 
dripping.

 Caution:

To prevent falls, maintain a stable footing when operating the unit.

3.6. Ventilation

For LOSSNAY combination

    The following 2 patterns of operation is available.

•  

Run the ventilator together with indoor unit.

•  

Run the ventilator independently.

Note: (for wireless remote controller)

 

 

 Running the ventilator independently is not available.

 

 

 No indication on the remote controller.

Summary of Contents for Mr.Slim PCA-RP HAQ

Page 1: ...u de airconditioner gebruikt MANUAL DE INSTRUCCIONES Lea este manual de instrucciones hasta el final antes de poner en marcha la unidad de aire acondicionado para garantizar un uso seguro y correcto...

Page 2: ...top operation turn off the power switch and contact your dealer Never insert fingers sticks etc into the intakes or outlets If you detect odd smells stop using the unit turn off the power switch and c...

Page 3: ...er Manual Manual Manual Filter Normal Long life Oil Filter cleaning indication 100 hr 2 500 hr 100 hr 2 Parts Names PCA RP KAQ Ceiling Suspended Vane Air outlet Air intake Filter Inside of Air intake...

Page 4: ...ing up the Main menu 5 Backlit LCD Operation settings will appear When the backlight is off pressing any button turns the backlight on and it will stay lit for a certain period of time depending on th...

Page 5: ...e 2 Appears when the buttons are locked Full mode All icons are displayed for explanation Fri Mode Temp Fan Room Cool Auto Set temp Basic mode Fri Cool Mode Temp Fan Auto Set temp 2 1 5 6 7 8 9 0 1 3...

Page 6: ...te controller wet or leave it in a location with high hu midity To avoid misplacing the remote controller install the holder included with the remote controller on a wall and be sure to always place t...

Page 7: ...ted to the same outdoor unit are already operated in a different mode In this case the rest of the unit in the same group can only be operated in the same mode Automatic operation According to a set t...

Page 8: ...n automatic fan speed is not set at default setting It is not necessary to set for wired remote controller with automatic fan speed at default setting 1 Press the SET button with something sharp at th...

Page 9: ...ng to move the vanes up and down automatically When set to Step 1 through Step 5 the vane will be fixed at the se lected angle under the vane setting icon This icon will appear when the vane is set to...

Page 10: ...tion switch heating D Emergency operation switch cooling E Receiver Starting operation To operate the cooling mode press the button D for more than 2 seconds To operate the heating mode press the butt...

Page 11: ...filter sign is reset the cumulative operation time of all units will be reset The icon is scheduled to appear after a certain duration of opera tion based on the premise that the indoor units are inst...

Page 12: ...leaning the frame of the oil filter Tools to be prepared Protective goods such as a rubber glove Scrubbing brush or brush Note Avoid using a metal scrubbing brush or brush since the aluminum materials...

Page 13: ...is emitted from the indoor unit If the indoor temperature and the humidity are high this condition may occur when operation starts During defrosting mode cool airflow may blow down and appear like a m...

Page 14: ...ler Be sure to provide the dealer with the model name 7 Trouble Shooting Model PKA RP35HAL PKA RP50HAL Power source voltage V Frequency Hz N 230 50 Rated Input Indoor only kW 0 04 0 03 0 04 0 03 Rated...

Page 15: ...146 1 PAR 31MAA 8 R410A 1 146 2 147 3 151 4 154 5 154 6 155 7 157 8 158...

Page 16: ...147 PKA RP HAL PCA RP KAQ PCA RP HAQ 3 4 2 100 2 500 100 2 PCA RP KAQ PKA RP HAL PCA RP HAQ...

Page 17: ...5 6 7 8 9 0 Fri Room Set temp Mode Temp Fan Cool Auto Main Main display Cursor Page Main menu Vane Louver Vent Lossnay High power Timer Weekly timer OU silent mode 7 8 9 0 7 8 9 0 1 2 3 4 5 6 7 F1 8...

Page 18: ...149 2 Fri Mode Temp Fan Room Cool Auto Set temp Fri Cool Mode Temp Fan Auto Set temp 2 1 5 6 7 8 9 0 1 3 9 4 2 3 4 5 6 7 8 1 2 3 4 5 1 2 3 4 5 6 7 8 9 0 1 2 3 4 5 6 7 1 8 9...

Page 19: ...150 1 AAA 2 Reset 1 2 3 2 7 45 AAA Reset Reset ON OFF Test Reset Power Earth Service Panel Indoor Outdoor Connection wire Ref Pipes...

Page 20: ...at Cool Dry Fan Auto Heat 2 0 C 15 2 0 C 15 15 2 0 C 2 0 C 15 F1 F2 F3 F4 Cool Room Auto Set temp Mode Temp Fan Fri 3 3 Cool Dry Heat Auto Cool Room28 5 Auto Set temp Mode Temp Fan Fri 28 5 0 5 F1 F2...

Page 21: ...nt mode F1 F2 Auto 1 STAND BY DEFROST 2 3 HEAT 4 DRY 1 SET MODELSELECT A 2 AUTO STOP B 01 3 02 02 ON OFF 2 4 SET MODELSELECT 3 ON OFF TEMP RESET SET CLOCK MODELSELECT FAN VANE TEST RUN AUTO STOP AUTO...

Page 22: ...ouver Vent Lossnay High power Timer Weekly timer OU silent mode Vane Louver Vent Lossnay Lossnay 152 F1 F2 F3 F4 Fri Swing Off Off Louver Vent Vane Cool Room Auto Set temp Mode Temp Fan Fri F1 F2 F3 F...

Page 23: ...154 4 1 4 E O SW 5 PKA RP HAL Fig 5 1 Fig 5 2 Fig 5 1 A DEFROST STAND BY B C D E D 2 C 2 D C 2 Fig 5 2 A DEFROST STAND BY OPAH EB l B E EH I C D COOL HEAT 5 STOP 5 COOL HEAT 24 C 24 C 4 5...

Page 24: ...k Filter information Error information F1 F2 F3 F4 Main menu Filter information Reset Please clean the filter Press Reset button after filter cleaning F1 F2 F3 F4 Filter information Filter information...

Page 25: ...156 6 1 1 2 A B C D B A D C RP71 3 RP125 4 PCA RP HAQ 1 1 2 1 2 1 2 3 PAC SG38KF 12 4 5 A C B D 3 1 100 2 1 10 50 C 1 PKA RP HAL PCA RP KAQ PCA RP HAQ...

Page 26: ...157 7 10 1 ON OFF ON OFF ON OFF ON OFF ON OFF ON OFF PLEASE WAIT 3...

Page 27: ...0 06 0 06 0 06 0 09 0 09 0 11 0 11 0 14 0 14 A 0 29 0 27 0 37 0 37 0 39 0 39 0 42 0 42 0 65 0 65 0 76 0 76 0 90 0 90 230 960 1280 1600 680 2 1 3 10 11 12 14 10 11 13 15 15 16 17 19 16 17 18 20 22 24...

Page 28: ...ra compilar o ficheiro t cnico o seguinte Vores autoriserede repr sentant i EU som er autoriseret til udarbejdelse af den tekniske fil er f l gende V r EG representant som r auktoriserad att sammanst...

Page 29: ...C9612 JIS B8616 ISO 5151 T1 et ISO 13523 T1 SVENSKA Engelska r originalspr ket De vriga spr kversionerna r vers ttningar av ori ginalet F RSIKTIGHET K ldmedelsl ckage kan leda till kv vning Tillhanda...

Page 30: ...ATE Sequential number for each unit 00001 99999 A indoor unit A Month of manufacture 4 5 6 7 8 9 X 10 Y 11 Z 12 1 2 3 Last digit of the company s fiscal year western calendar 2014 4 2015 5 00001 99999...

Page 31: ...I CHIYODA KU TOKYO 100 8310 JAPAN Authorized representative in EU MITSUBISHI EUROPE B V HARMAN HOUSE 1 GEORGE STREET UXBRIDE MIDDLESEX UB8 1QQ U K 115054 52 1 Please be sure to put the contact address...

Reviews: