3
SEQUENCE PROGRAM EXECUTION
3.2 Concept of Scan Time
3
- 6
1
O
verv
iew
2
Per
fo
rma
nce
S
p
ecifica
tio
n
3
S
equ
en
ce P
ro
g
ra
m
Co
nfig
ura
tio
n a
nd
E
xecut
io
n Co
nd
iti
o
ns
4
I/O N
unb
er
Assig
n
m
e
nt
5
Me
mor
ie
s a
nd
File
s
Ha
nd
led
by CP
U Mo
du
le
6
Func
tions
7
Co
mmu
nica
tion
with
Inte
llig
en
t Fu
n
ct
ion
Mo
du
le
8
P
a
ram
et
e
rs
(2) WDT (Watchdog timer)
The watchdog timer (hereafter abbreviated to the WDT) watches the scan time.
The default value is 200ms.
(a) WDT error
A WDT error is 10ms.
When the WDT (t) is set to 10ms, a "WDT ERROR" occurs within a scan time
range of 10ms<t<20ms.
(b) WDT Setting
The WDT setting can be changed within a range of 10ms to 2000ms in the PLC
RAS of the PLC parameter dialog box. (Setting unit: 10ms)
(3) Function that repeats program at fixed intervals
The constant scan function (
Section 6.9) allows a program to be executed
repeatedly at fixed intervals.
When the constant scan is set, a program is executed at intervals of the preset
constant scan time.
Diagram 3.7 PLC RAS (WDT Setting)
Summary of Contents for MELSEC QS Series
Page 1: ......
Page 2: ......
Page 24: ...A 22 Memo ...
Page 258: ...Index 3 Memo ...
Page 263: ......
Page 264: ......