9
DEVICE EXPLANATION
9.2 Internal User Devices
9.2.8 Timer (T)
9
- 21
9
D
e
vi
ce
Exp
lana
tion
10
CP
U Mo
du
le
Pr
oce
ssing
Ti
m
e
11
P
ro
ced
ur
e f
o
r W
rit
in
g
Pr
og
ra
m t
o CP
U Mo
du
le
App
e
nd
ic
es
In
de
x
(7) Timer Processing and accuracy
(a) Processing method
When an OUT T instruction is executed, the following is processed: timer coil
ON/OFF, current value update and contact ON/OFF processing. Timer current
value update and contact ON/OFF processing are not performed at END
processing.
Diagram 9.21 Processing at execution of OUT TO instruction
X100
T0
K10
END
OUT T0
END
[Processing at execution of OUT T0 instruction]
[Ladder example]
Sequence
program
Processing content
Coil ON/OFF
Current value update
Contact ON/OFF