26
4 FUNCTIONS
4.2 Processing of Each Function
4.2
Processing of Each Function
The functions are processed in the order shown below depending on the mode. If multiple functions are enabled, the output of
the first processed function is used as the input of the next function.
• Normal mode
For the resistance temperature detector input range, or thermocouple input range, the conversion is stopped
when a disconnection is detected. The digital output value, digital operation value, logging data, maximum
value, and minimum value in this case are as follows:
• Digital output value: The values are stored according to the setting in conversion setting at disconnection
detection.
• Digital operation value: The calculated values are stored according to the scaling function and shift function
in digital output value.
• Logging data: The digital output values or digital operation value are stored according to the logging data
setting
• Maximum value and minimum value: The values are updated with the maximum and minimum values of the
digital operation value
In the use of the input signal error detection function, conversion is stopped if an input signal error is detected.
In this case, the digital output values, digital operation values, and maximum and minimum values are not
updated. The values obtained before the input signal error is detected are held. Conversion is resumed after
restoration from the errors in the input signal. The digital output value or digital operation value before the
input signal error was detected is stored in logging data depending on the logging data setting.
CH
Logging
data
CH
Maximum
value
CH
Minimum
value
CH
Digital
operation value
Analog input
(CH1 to CH16)
A/D conversion
method
Input signal
error detection
function
Disconnection
detection
function
Refer to
4.8 Disconnection
Detection Function
Sampling
processing
Count average
Time average
Alert output
function
Moving average
Digital clipping
function
Scaling function
Shift function
Maximum value/
minimum value
hold function
Logging function
CH
Digital
output value
Rate
alarm
Process
alarm
Refer to
4.9 Input Signal
Error Detection
Function
Summary of Contents for MELSEC iQ-F
Page 1: ...MELSEC iQ F FX5 User s Manual Analog Control Intelligent function module ...
Page 2: ......
Page 9: ...7 MEMO ...
Page 181: ......