58
4 SYSTEM CONFIGURATION
4.5 Rules of System Configuration and Examples of Reconfiguration
Result check
Because calculation results for 5 V DC or 24 V DC current consumption are negative, reconfiguration is necessary.
The judgment procedure after reconfiguration is explained on the following pages.
System reconfiguration example
If current consumption of the 5 V DC or 24 V DC power supply is insufficient with the CPU module only, use an extension
power supply module.
Reconfigure the example system configuration using an extension power supply module.
1150 mA
-
720 mA
CPU module
Current consumption
-430 mA
=
Calculation result
NG
Capacity of 5 V DC
power supply
Total of current
consumed by extension
module
360 mA
-
500 mA
CPU module
Current consumption
140 mA
=
Calculation result
OK
Capacity of 24 V
DC power supply
Total of current
consumed by extension
module
FX5-C16EYT/D
FX5-C16EYT/D
FX5-C16EX/D
FX5UC-32MT/D
FX5-232ADP
FX5-485ADP
FX5-CNV-BUS
FX5-40SSC-S
FX5-CNV-IFC
FX3U-1PG
FX3U-4AD
FX3U-128ASL-M
FX3U-4LC
FX3U-64CCL
CC-Link
FX5-C16EYT/D
FX5-C1PS-5V
To CC-Link
master
station
The number of transmission points
setting for AnyWireASLINK
64 points
Remote
I/O station
Remote
I/O station
Remote
I/O station
Summary of Contents for MELSEC iQ-F FX5UC
Page 1: ...MELSEC iQ F FX5UC User s Manual Hardware ...
Page 2: ......
Page 15: ...13 CONTENTS ...
Page 183: ......