642
9 HIGH-SPEED COUNTER INSTRUCTION
9.1 High-speed Processing Instruction
Start/stop of the 32-bit data high-speed I/O function
DHIOEN(P)
These instructions control the start and stop operations of a high-speed I/O function.
Setting data
■
Descriptions, ranges, and data types
■
Applicable devices
Processing details
Specify the number of the function to be started or stopped in (s1), the bit of the channel to be started in (s2), and the bit of the
channel to be stopped in (s3).
The following table shows the function numbers which can be specified in (s1).
*1
When high-speed counter (function number: 0) is stopped during function operation, the function continues to operate, but nothing will
be processed.
*2
When multi-output high-speed comparison table (function number: 30) is stopped, high-speed counter of the same ch is also stopped.
The following table shows the values which can be specified in (s2) and (s3) for each function number.
Function number 0
The counting start and stop of a high-speed counter can be controlled for each channel of the high-speed counter.
Ex.
To start CH3, set 04H in (s2). To stop it, set 04H in (s3).
To start CH1, CH4, and CH5, set 19H in (s2). To stop them, set 19H in (s3).
To start CH1 and CH4 and to stop CH5, set 09H in (s2) and set 10H in (s3).
Ladder diagram
Structured text
ENO:=DHIOEN(EN,s1,s2,s3);
ENO:=DHIOENP(EN,s1,s2,s3);
Operand
Description
Range
Data type
Data type (label)
(s1)
Function number to be started or stopped
K0 to 50
16-bit signed binary
ANY16
(s2)
Set the bit of the channel number where the function is started.
-2147483648 to
+2147483647
32-bit signed binary
ANY32
(s3)
Set the bit of the channel number where the function is stopped.
-2147483648 to
+2147483647
32-bit signed binary
ANY32
Operand
Bit
Word
Double word
Indirect
specification
Constant
Others
X, Y, M, L,
SM, F, B, SB
U
\G
T, ST,
C, LC
T, ST, C, D,
W, SD, SW, R
U
\G
Z
LC
LZ
K, H
E
$
(s1)
(s2)
(s3)
Function
number
Function name
0
High-speed counter
Pulse density/rotation speed measurement
High-speed comparison table
Multi-output high-speed comparison table
40
Pulse width measurement
50
PWM
Bit position
b15
b14
b13
b12
b11
b10
b9
b8
b7
b6
b5
b4
b3
b2
b1
b0
CH8
CH7
CH6
CH5
CH4
CH3
CH2
CH1
(s1)
(s2)
(s3)
Summary of Contents for MELSEC iQ-F FX5 series
Page 1: ...MELSEC iQ F FX5 Series Programming Manual Instructions Standard Functions Function Blocks ...
Page 2: ......
Page 21: ...19 PART 1 PART 1 OVERVIEW Part 1 consists of the following chapter 1 OVERVIEW ...
Page 98: ...96 4 STANDARD FUNCTIONS FUNCTION BLOCKS 4 2 Standard Function Blocks MEMO ...
Page 840: ...838 23 TIME DATA FUNCTIONS 23 4 Division MEMO ...
Page 887: ......