Preset 0 (-10V to +10V)
Preset 1 (+4mA to +20mA)
Preset 2 (-20mA to +20mA)
Analog inputs continued.....
Digital
Output
+1600
+1000
+32mA
+20mA
-1000
-1600
-20mA
-32mA
Current
Input
Current
Input
+1750
+1000
+32
mA
+20
mA
+4
mA
Digital
Output
Miscellaneous
Item
Specification
Isolation
Photo-coupler isolation between analog and digital circuits.
DC/DC converter isolation of power from FX base unit.
No isolation between analog channels.
Number of occupied I/O points
8 points taken from the FX expansion bus (can be either inputs or outputs)
Digital
Output
+10V
+10.235V
Voltage Input
+2047
+2000
-10.24V
-10V
-2000
-2048
NOTE: Preset ranges are selected by an appropriate setting in buffer memory of the analog block.
Current/Voltage input selection must match the correct input terminal connections.
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com