1.1 External dimensions
Weight : Approx. 0.5kg (1.1 lbs) Dimensions : mm (inches)
Any connection to these terminals
may damage the FX-2DA.
125 (4.92)
140 (5.51)
63 (2.48)
73 (2.87)
10 (0.39)
95 (3.74)
Extension cable
and connector
24V LED
D-A LED
*4 Connect the ground terminal on the FX-2DA with
the ground terminal on the base unit of the
programmable controller. Use class 3 grounding
on the base unit, if available.
*1 Use a twisted pair shielded cable for the analog
output. This cable should be wired away from
power lines or any other lines which could induce
noise.
Caution;
(a) The same output channel cannot drive current
and voltage output loads at the same time!
(b) Shorting the voltage output terminals may da-
mage the unit!
FX-2DA special function block
V
V
I
I
+
-
+
-
*2
Groove for
35mm (1.38)
wide DIN rail
2-5.5mm (0.22)
hole
M3.5 (0.14)
terminal screws
Wiring
2
*2 Apply 1-point grounding at the load side of the
output cable (class 3 grounding: 100
Ω
or less). If
electrical noise is caused from grounding,
disconnect from grounding.
*3 If electrical noise or a voltage ripple exists at the
output, connect a smoothing capacitor of 0.1 to
0.47
µ
F, 25V.
CH1
DC/DC
converter
+15V
AG
-15V
+24V
0V
DC24V ±10% 130mA
*4
PC
Extension cable
Class 3
Grounding
(100
Ω
or less)
V
V
I
I
+
-
+
-
CH2
Current output
*2
*1
Recorder,
etc.
Inverter,
etc.
*3
*1
Voltage output
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com