7

5.2 PROFIBUS Cable Wiring

This section explains the wiring to PROFIBUS connector for the 
A1SJ71PB93D

(1) Pin assignments for the connector

*1

The signals are used when termination resistors are connected.

(2) Wiring

 • Please use the PROFIBUS cable (Type A) with braided shield.

(3) Termination resistor

Pin No.

Name

Application

1

SHIELD

Shield, Protective Ground

2

Vacancy

3

RxD/TxD-P

Receive/Transmit Data-P

4

Vacancy

5

DGND *1

Data Ground

6

VP *1

Voltage-Plus

7

Vacancy

8

RxD/TxD-N

Receive/Transmit Data-N

9

Vacancy

PROFIBUS cable

A1SJ71PB93D

8

3

1

RxD/TxD-N

RxD/TxD-P

SHIELD

2%, min1/4W

2%, min1/4W

2%, min1/4W

 = 390

d

R

 = 220

tA

R

 = 390

u

R

RxD/TxD-P (3)

DGND (5)

RxD/TxD-N (8)

VP (6)

Summary of Contents for MELSEC-A A1SJ71PB93D

Page 1: ...ose programmable controller MELSEC Series 2001 MITSUBISHI ELECTRIC CORPORATION PROFIBUS DP Slave Module Prior to use please read both this manual and detailed manual thoroughly and familiarize yoursel...

Page 2: ...the PROFIBUS DP the status of the faulty station is as follows Configure an interlock circuit in the sequence program using the communication status information input X1 so that the system can operat...

Page 3: ...ment outside the range of the general specifications may cause electric shock fire malfunction and damage to or deterioration of the product Load the module by securely inserting the module fixing hoo...

Page 4: ...Unless the cable is thus protected or secured the module or the cable could be damaged when the cable swings moves or it is strained with careless pulls or it could cause malfunction when the cable co...

Page 5: ...e controller in all directions Failure to do so can cause a malfunction Be sure to shut off all phases of the external power supply before mounting or removing the module Failure to do so may result i...

Page 6: ...NDED OR EXCLUDED BY INSTRUCTIONS PRECAUTIONS OR WARNING CONTAINED IN MITSUBISHI S USER INSTRUCTION AND OR SAFETY MANUALS TECHNICAL BULLETINS AND GUIDELINES FOR the PRODUCT Prohibited Application Prohi...

Page 7: ...s provided that the usage of the PRODUCT is limited only for the specific applications agreed to by Mitsubishi and provided further that no special quality assurance or fail safe redundant or other sa...

Page 8: ...COMPLIANCE WITH EMC AND LOW VOLTAGE DIRECTIVES SAFETY PRECAUTIONS Chinese CONDITIONS OF USE FOR THE PRODUCT This manual confers no industrial property rights or any rights of any other kind nor does i...

Page 9: ...S 1 OVERVIEW 1 2 PERFORMANCE SPECIFICATIONS 1 3 INSTALLATION 3 3 1 Handling Precautions 3 4 PART NAMES AND SETTINGS 4 5 WIRING 6 5 1 Precautions Against Wiring 6 5 2 PROFIBUS Cable Wiring 7 6 OUTLINE...

Page 10: ...equipment certain measures may be necessary Please refer to one of the following manuals User s manual for the CPU module used User s manual hardware for the CPU module or base unit used The CE mark o...

Page 11: ...Model A1SJ71PB93D PROFIBUS DP station type Slave station Transmission specifications Electrical standards and characteristics Complies with EIA RS485 Medium Shielded twisted cable Type A Network conf...

Page 12: ...dule user s manual Transmission specifications Maximum number of repeaters network 3 units 2 Maximum number of stations segment 32 stations including repeaters Number of connection nodes segments 32 S...

Page 13: ...e it is made of resin 2 Do not remove the PCB of each module from its case This may cause a failure in the module 3 Be careful not to let foreign objects such as wire burrs enter the module during wir...

Page 14: ...4 4 PART NAMES AND SETTINGS Following is an explanation of the A1SJ71PB93D part names and settings b a...

Page 15: ...us On Normal Off Module WDT error occurrence ERR On Parameter setting error or module error occurrence Off Normal SYNC On During SYNC mode FREEZE On During FREEZE mode DIA On During extended fault not...

Page 16: ...e the module may be susceptible to an influence of noise and surge induction 2 The wires from the input output modules of the PLC should be away from the communication cable as far as possible as show...

Page 17: ...PROFIBUS cable Type A with braided shield 3 Termination resistor Pin No Name Application 1 SHIELD Shield Protective Ground 2 Vacancy 3 RxD TxD P Receive Transmit Data P 4 Vacancy 5 DGND 1 Data Ground...

Page 18: ...8 6 OUTLINE DRAWINGS Unit mm inch 4 0 16 130 5 12 93 6 3 69 6 5 0 26 34 5 1 36...

Page 19: ...9 MEMO...

Page 20: ...s Bouvets F 92741 Nanterre Cedex France Tel 33 1 5568 5568 South Africa Circuit Breaker Industries Ltd Private Bag 2016 ZA 1600 Isando South Africa Tel 27 11 928 2000 China Mitsubishi Electric Automat...

Reviews: