background image

10

A

90

°

6. INDOOR/OUTDOOR UNIT CONNECTION FINISHING AND TEST RUN

6-1

Tools dedicated for the air conditioner with R410A refrigerant

The following tools are required for R410A refrigerant. Some R22 tools can be substituted for R410A tools.
The diameter of the service port on the stop valve in outdoor unit has been changed to prevent any other
refrigerant being charged into the unit. (Cap size has been changed from 7/16 UNF with 20 threads to 1/2 UNF
with 20 threads.)

R410A tools

Can R22 tools be used?

Description

R410A has high pressures beyond the measurement range of existing
gauges.

Gauge manifold

No

Port diameters have been changed to prevent any other refrigerant from
being charged into the unit.

Charge hose

No

Hose material and cap size have been changed to improve the pressure
resistance.

Gas leak detector

No

Dedicated for HFC refrigerant.

Torque wrench

Yes

1/4

No

1/2, 5/8

Flare tool

Yes

Clamp bar hole has been enlarged to reinforce the spring strength in the
tool.

Flare gauge

New

Provided for flaring work (to be used with R22 flare tool).

Vacuum pump adaptor

New

Provided to prevent the back flow of oil. This adapter enables you to use
existing vacuum pumps.

New

It is difficult to measure R410A with a charging cylinder because the refrig-
erant bubbles due to high pressure and high-speed vaporization.

No: Not substitutable for R410A Yes: Substitutable for R410A

Electronic scale for re-
frigerant charging

6-2

FLARING WORK

• Main cause of gas leakage is defect in flaring work.

Carry out correct flaring work in the following procedure.

2. Burrs removal

• Completely remove all burrs from the cut cross section of

pipe.

• Put the end of the copper pipe to downward direction as

you remove burrs in order to avoid to let burrs drop in the
piping.

Copper pipe

Good

No good

Tilted

Uneven

Burred

3. Putting nut on

• Remove flare nuts attached to indoor and outdoor units,

then put them on pipe having completed burr removal.
(not possible to put them on after flaring work)

• Flare nut for R410A pipe differs from R22 pipe. Refer to the

following table for detail.

Burr

Copper pipe

Spare
reamer

Pipe
cutter

4. Flaring work

• Carry out flaring work using flaring tool as shown below.

Flare nut

Copper pipe

1. Pipe cutting

• Cut the copper pipe correctly with pipe cutter.

• Firmly hold copper pipe in a die in the dimension shown in

the table above.

5. Check

• Compare the flared work with figure below.
• If flare is noted to be defective, cut off the flared section

and do flaring work again.

Die

Copper pipe

Flare nut

Die

Copper pipe

York

Flaring tool

Wing nut type

Clutch type

A (mm)

Outside

Conventional flare tool

diameter

Clutch type

Wing nut type

ø6.35 mm

0 to 0.5

1.0 to 1.5

1.5 to 2.0

ø12.7 mm

0 to 0.5

1.0 to 1.5

2.0 to 2.5

ø15.88 mm

0 to 0.5

1.0 to 1.5

2.0 to 2.5

Flare tool for

R410A clutch type

Smooth all around

Even length
all around

Inside is shining
without any scratches.

mm

inch

R410A

R22

ø6.35

1/4

17

17

ø12.7

1/2

26

24

ø15.88

5/8

29

27

Summary of Contents for MCFZ-A18WV

Page 1: ...C utilized R410A CONTENTS 1 THE FOLLOWING SHOULD ALWAYS BE OBSERVED FOR SAFETY 2 2 SELECTING THE INSTALLATION LOCATION 2 3 INSTALLATION DIAGRAM ACCESSORIES 3 4 INDOOR UNIT INSTALLATION 4 5 OUTDOOR UNI...

Page 2: ...frigerant circuit Any presence of foreign substance such as air can cause abnormal pressure rise or an explo sion 330 mm 360 mm 500 mm 840 mm 1 THE FOLLOWING SHOULD ALWAYS BE OBSERVED FOR SAFETY Pleas...

Page 3: ...gerant pipe 1 set B Indoor outdoor connecting wire 2 core 1 0 mm2 1 C Piping tape 1 D Drain pipe PVC pipe OD 26 1 E Pipe fixing band for refrigerant pipe The quantity depends on the pipe length 2 to 5...

Page 4: ...lack of thickness may cause dew drippage 4 1 A CASE OF SUSPENDING INDOOR UNIT FROM THE CEILING 4 1 1 MOUNTING INSTALLATION PLATE FIXING BOLTS 4 INDOOR UNIT INSTALLATION 1 Determine the locations of in...

Page 5: ...own in Fig 2 Be sure to confirm letters FRONT in installation plates 1 set FRONT side to air outlet side of indoor unit a FRONT 1 Installation plate 2 In case of fixing installation plates 1 above the...

Page 6: ...m the dimensions as below 4 2 4 FRONT GRILLE REMOVAL See to 4 1 4 Page 5 4 2 5 OPENING KNOCKOUT HOLE See to 4 1 5 Page 5 Installation pattern Remove installation pattern after installing Horizontal ba...

Page 7: ...e to fix the cable by cable clamp 3 Replace the terminal cover securely Cable clamp Screw Terminal cover Warning Attach the electrical part cover securely If it is attached incorrectly it could result...

Page 8: ...ve 8 Drain pipe cover D Drain pipe VP 20 c 8 D b a d b a 30 2 In case of connecting drain pipe D to drain joint bush through drain hose Drain hose 7 which is contained in accessories is flexible so us...

Page 9: ...or less 25 m or less Power supply cord Specification Indoor and Outdoor connecting wire Specification 3 core 2 5 mm2 or more in conformity with Design 245 IEC 57 3 core 4 0 mm2 or more in conformity w...

Page 10: ...ble for R410A Electronic scale for re frigerant charging 6 2 FLARING WORK Main cause of gas leakage is defect in flaring work Carry out correct flaring work in the following procedure 2 Burrs removal...

Page 11: ...liquid pipe and the gas pipe between the indoor and the outdoor unit Remove the service port cap of the stop valve on the side of the outdoor unit gas pipe The stop valve will not work in it initial...

Page 12: ...Operating Instruction Book EMERGENCY OPERATION switch 6 5 TEST RUN Before performing the test run recheck for any wrong wiring Wrong wiring prevents normal operation or results in blown fuse disabling...

Page 13: ...rge refrigerant into the atmosphere during installation reinstallation or re pairs to the refrigerant circuit For additional charging charge the refrigerant from liquid phase of the gas cylinder If th...

Page 14: ...TOKYO 100 8310 JAPAN This product is designed and intended for use in the residential commercial and light industrial environment The product at hand is based on the following EU regulations Low Volta...

Reviews: