5. CONNECTION TO FUJI TEMPERATURE CONTROLLER
5.3 Connection Diagram
5 - 11
5
C
O
NNE
CTION T
O
FUJI TEMPE
R
A
T
U
R
E CON
T
ROLLER
(7) RS-485 connection diagram 7)
*1
Pin No. of temperature controller differs depending on the model. Refer to the following table.
*2
Terminating resistor should be provided for a temperature controller which will be a terminal.
*3
Set the terminating resistor of GOT side which will be a terminal.
■
Connecting terminating resistors
*4
Connect FG grounding to the appropriate part of a cable shield line.
Precautions when preparing a cable
(1) Cable length
The length of the RS-485 cable must be 500m or less.
(2) GOT side connector
For the GOT side connector, refer to the following.
1.4.1 GOT connector specifications
(3) FUJI temperature controller side connector
Use the connector compatible with the FUJI
temperature controller side.
For details, refer to the user's manual of the FUJI
temperature controller.
Connecting terminating resistors
(1) GOT side
Set the terminating resistor setting switch of the GOT
main unit to "100 OHM".
For the procedure to set the terminating resistor, refer
to the following.
1.4.3 Terminating resistors of GOT
(2) FUJI temperature controller side
When connecting a FUJI temperature controller to the
GOT, a terminating resistor must be connected.
5.5 Temperature Controller Side Setting
Signal name
Model of temperature controller
PXR3
PXR4
PXR5/9
PXG4
PXG5/9
PXH9
Pin No.
Pin No.
Pin No.
Pin No.
Pin No.
Pin No.
+
15
7
1
7
1
14
-
14
8
2
8
2
16
GOT side
*3
SDA
SDB
RDA
RDB
SG
RSA
CSA
RSB
CSB
1
6
2
7
5
3
4
8
9
+*
1
-*
1
+*1
-*1
Temperature
controller side
Temperature
controller side
Terminating resistor(100
Ω
1/2W)
*2
*4
*4
Summary of Contents for GOT2000Series
Page 2: ......
Page 17: ...A 15 REVISIONS WARRANTY...
Page 52: ...1 30 1 PREPARATORY PROCEDURES FOR MONITORING 1 6 Checking for Normal Monitoring...
Page 54: ......
Page 78: ...3 10 3 CONNECTION TO HITACHI PLC 3 6 Device Range that Can Be Set...
Page 100: ...4 22 4 CONNECTION TO FUJI PLC 4 7 Precautions...
Page 174: ...7 24 7 CONNECTION TO YOKOGAWA PLC 7 4 Device Range that Can Be Set...
Page 262: ...9 54 9 CONNECTION TO RKC TEMPERATURE CONTROLLER 9 7 Precautions...
Page 280: ...10 18 10 CONNECTION TO ALLEN BRADLEY PLC 10 4 Device Range that Can Be Set...
Page 296: ...11 16 11 CONNECTION TO GE PLC 11 7 Precautions...
Page 308: ...12 12 12 CONNECTION TO LS INDUSTRIAL SYSTEMS PLC 12 6 Device Range that Can Be Set...
Page 332: ...14 18 14 CONNECTION TO SIEMENS PLC 14 4 Device Range that Can Be Set...
Page 334: ...REVISIONS 2...
Page 337: ......