17 - 2
17.1 Daily Inspection
17
M
A
IN
TE
N
A
N
C
E AN
D
IN
SP
ECTIO
N
18
ERROR MESSA
GE
AND S
YSTEM
ALARM
APP
ENDICE
S
17.1 Daily Inspection
Daily inspection items
Refer to the following for the model names of the protection sheet or the replacement procedure.
17.2 Periodic Inspection
Yearly or half-yearly inspection items
The following inspection should also be performed when equipment has been moved or modified or the
wiring changed.
No.
Inspection Item
Inspection
Method
Criterion
Action
1
GOT mounting status
Check for loose
mounting screws.
Securely mounted
Retighten screws within the
specified torque range
2
Connection
status
Loose terminal screws
Retighten screws
with screwdriver
Not loose
Retighten terminal screws
Proximate solderless
terminals
Visual check
Proper intervals
Correct
Loose connectors
Visual check
Not loose
Retighten connector fixing
screws
3
Usage
status
Dirt on protection sheet
Visual check
Not outstanding
Replace with new one
Foreign material
attachment
Visual check
No foreign matter
sticking
Remove clean
No.
Inspection Item
Inspection Method
Criterion
Action
1
Surrounding
environment
Ambient
temperature
Make measurement
with thermometer or
hygrometer
Measure corrosive
gas
Display section 0 to 50°C
For use in control panel,
temperature inside control
panel is ambient
temperature
Other portions
0 to 55°C
Ambient
humidity
10 to 90%RH
Atmosphere
No corrosive gas
2
Power supply voltage check
24VDC Measure
voltage across
terminals.
20.4 to 26.4VDC
Change supply power
3
Mounting
status
Looseness
Move module
Should be mounted firmly
Retighten screws
Dirt, foreign
matter
Visual check
No dirt, foreign matter
sticking
Remove, clean
4
Connection
status
Loose
terminal
screws
Retighten screws with
screwdriver
Not loose
Retighten terminal screws
Proximate
solderless
terminals
Visual check
Proper intervals
Correct
Loose
connectors
Visual check
Not loose
Retighten connector fixing
screws
5
Battery
Check the system
alarm (error code:
500) report on the
Alarm Information
screen (Section 13.4
Alarm Information).
(Preventive maintenance)
Replace with new battery
when the current battery
has reached the specified
life span, even if battery
voltage is not displayed.
Summary of Contents for GOT1000 GT11
Page 1: ......
Page 2: ......
Page 251: ...Index 2 U Utility function list 9 2 W Wiring 7 1...
Page 252: ...Index 3 MEMO...
Page 255: ......