background image

F940GOT Series(F940GOT-*WD-E)

Installation Manual

JY992D94201B

This manual contains text, diagrams and explanations which will guide the reader in the correct
installation, safe use and operation of the F94*GOT-*WD-E and should be read and understood before
attempting to install or use the unit. Further information can be found in the associated manuals list below.

Specifications are subject to change without notice

Guidelines for the Safety of the User and Protection of the 
F940GOT-*WD-E

This manual has been written to be used by trained and competent personnel. The definition of such a
person or persons is as follows:

a) Any engineer using the product associated with this manual, should be of a competent nature,

trained and qualified to the local and national standards. These engineers should be fully aware of
all aspects of safety with regards to automated equipment.

b) Any commissioning or service engineer must be of a competent nature, trained and qualified to

the local and national standards.

c)

All operators of the completed equipment should be trained to use that product in a safe and 
co-ordinated manner in compliance to established safety practices.

Note: The term ‘completed equipment’ refers to a third party constructed device which contains or uses

the product associated with this manual.

Note’s on the Symbols Used in this Manual

At various times through out this manual certain symbols will be used to highlight points of information
which are intended to ensure the users personal safety and protect the integrity of equipment.

1) Indicates that the identified danger WILL cause physical and property damage.

2) Indicates that the identified danger could POSSIBLY cause physical and property

damage.

Under no circumstances will Mitsubishi Electric be liable or responsible for any consequential damage
that may arise as a result of the installation or use of this equipment.

All examples and diagrams shown in this manual are intended only as an aid to understanding the
text, not to guarantee operation. Mitsubishi Electric will accept no responsibility for actual use of the
product based on these illustrative examples.

Owing to the very great variety in possible application of this equipment, you must satisfy yourself as
to its suitability for your specific application.

Associated Manuals

¤

Indispensable manual

¢

Either manual is necessary.

¨

Refer if necessary, please.

Refer to the manual of the connected programmable controller for details concerning that unit. 

Manual Name

Manual Number

Description

¤

GOT-F900 Series 
Operation Manual 

JY992D94701

This manual contains explanations for the 
operation and use of the GOT-F900 series 
graphic operation terminals.

¤

GOT-F900 Series 
Hardware Manual 
(connection diagram)

JY992D94801

This manual contains explanations for the 
wiring and installation, etc. of the GOT-F900 
series graphic operation terminals.

¢

FX-PCS-DU/WIN-E 
Operation Manual

JY992D68301

This manual contains explanations for the 
operation of FX-PCS-DU/WIN-E screen design 
software.

¢

SW*D5C-GOTR-PACKE
Operating Manual

-

This manual contains explanations for the 
operation of GT-Designer (SW*D5C-GOTR-
PACKE) screen design software.

¨

F9GT-40UMB
Manual

JY992D74101

This manual contains explanations for 
installation and operating procedure of F9GT-
40UMB data transfer adapter

1. Introduction

The F940GOT-*WD-E (hereafter called “GOT” or “F940GOT”) is
to be mounted on the face of a control panel or operations panel,
and connected to the programming por t (CPU por t) or the
communication port (communication units port) of a PLC.
Various devices can be monitored and PLC data changed
through the screens in the GOT. Several display screens are
built-in to the GOT, and additional personalized screens can be
created by the user.

1) The GOT can connect to MELSEC FX, A, QnA and Q PLCs

as well as a host of third party manufactured units. Further
information can be found in GOT-F900 Series Hardware
Manual.

2) Through the GOT, PLC user programs can be downloaded, uploaded and monitored in programming

software GX-Developer or FX-PCS/WIN-E on a personal computer. Further information can be found
in GOT-F900 Series Operation Manual.

3) Display screens are created using the following software. 

1.1 Product Lists

Caution

During abnormal communication (including cable break) when monitor is executed within the
GOT, communication between the GOT and programmable controller CPU is interrupted and
it is impossible to operate switches or devices in the PLC through the GOT. 
Communication and operation resumes when the GOT system is correctly configured.
DO NOT configure emergency stop or safety features to operate through the GOT, and be
sure that there is no adverse consequences in the event of a GOT - PLC communications
malfunction. 

Note;

Do not lay signal cables near high voltage power cables or allow them to share the same
trunking duct.
Otherwise effects of noise or surge induction are likely to take please. Keep a safe
distance of more than 100 mm from these wires.

Operate touch switches on the display screen by hand. 
DO NOT use excessive force, or attempt operate them with hard or pointed objects.
The tip of a screw driver, pen or similar object for example may break the screen. 

Software Name

Version

FX-PCS-DU/WIN-E

SW0PC-FXDU/WIN-E Version V2.00 or more

GT Designer

SW1D5C-GOTR-PACKE Version V 00A or more

Production Name

Description

F940GOT-SWD-E

Graphic operation terminal main unit: 
SWD: 8 colors
LWD: White and black

F940GOT-LWD-E

FX-50DU-CAB0

Communication cable (GOT 

 CPU port in FX

0

, FX

0S

, FX

1S

, FX

0N

, FX

1N

, FX

2N

 

or FX

2NC

 series PLC)

The connector on the GOT side is straight.
Cable length is 3m (9' 10").

FX-50DU-CAB0/EN

Communication cable (GOT 

 CPU port in FX

0

, FX

0S

, FX

1S

, FX

0N

, FX

1N

, FX

2N

 

or FX

2NC

 series PLC) 

The connector on the GOT side is straight. Cable length is 3m (9' 10").

FX-50DU-CAB0-**M

Communication cable (GOT 

 CPU port in FX

0

, FX

0S

, FX

1S

, FX

0N

, FX

1N

, FX

2N

 

or FX

2NC

 series PLC)

The connector on the GOT side is straight.
** M is cable length. 1M: 1m (3' 3"), 10M: 10m (32' 9"), 20M: 20m (65' 7"),

 30M: 30m (98' 5")

FX-40DU-CAB

Communication cable (GOT 

 CPU port in FX, FX

2C

, A or QnA series PLC)

The connector on the GOT side is straight. Cable length is 3m (9' 10").

FX-40DU-CAB0-**M

Communication cable (GOT 

 CPU port in FX, FX

2C

, A or QnA series PLC)

The connector on the GOT side is straight.
** M is cable length. 10M: 10m (32' 9"), 20M: 20m (65' 7"), 30M: 30m (98' 5")

QC30R2

Communication cable (GOT 

 CPU port in Q series PLC)

The connector on the GOT side is straight. Cable length is 3m (9' 10").

FX-232CAB-1

Data exchange cable (GOT 

 Personal computer <9-pin D-sub>)

FX-PCS-DU/WIN-E

Screen design software for Windows

GT-Designer

Screen design software for Windows (SW*D5C-GOTR-PAKE)

PM-20BL

Battery for keeping Alarm history, sampling and current time data

F9GT-40PSC

Transparent protection sheet for F940GOT (5 pieces)

F9GT-40LTS

Backlight for F940GOT

F9GT-40UMB

Data transfer adapter

P L C

P r o g r a m m i n g  

p o r t

G O T

1.2 Dimensions and Each Part Name

Dimensions: mm (inches)

MASS (Weight): 1 kg (2.2 lbs)

Accessory:

Mounting brackets, Tightening bolt (M3, 6 bolts), 
Packing seal for dust and water resistance

a) Display

b) Mounting bracket hole

c)

Communication ports

d) Mounting bracket and tightening bolt

e) PM-20BL battery

f)

Expansion interface

g) DC power supply terminal (M3)

h) Communication cable

i)

Packing seal

2. Specifications

2.1 General Specifications

Port

Description

RS-422

RS-422 Port for connecting PLC (including1:N connection) or communication 
(computer link) unit <9-pin D-sub>

RS232C

RS-232C port for connecting printer, bar-code reader or 1:N connection 
<9-pin D-sub>

Item

Specifications

Operating Temperature

0 ~ 50 °C (32 ~ 122 °F) 
[With expansion module: 0 ~ 40 °C (32 ~ 104 °F)]

Storage Temperature

-20 ~ 60 °C (-4 ~ 140 °F)

Humidity

35 ~ 85% Relative Humidity, No condensation

Vibration Resistance
 - intermittent vibration

Conforms to IEC 1131-2; 10 ~ 57 Hz: 0.075 mm Half Amplitude

                                       57 ~ 150 Hz: 9.8 m/s

2

 Acceleration

                  Sweep Count for X, Y, Z: 10 times (80 min. in each direction)

Vibration Resistance
 - Continuous vibration

Conforms to IEC 1131-2; 10 ~ 57 Hz: 0.035 mm Half Amplitude

                                       57 ~ 150 Hz: 4.9 m/s

2

 Acceleration

                  Sweep Count for X, Y, Z: 10 times (80 min in each direction)

Shock Resistance

Conforms to IEC 1131-2: 147m/s

2

 Acceleration, 

                                   3 times in each direction X, Y, and Z

Noise Immunity

1000 Vp-p, 1micro second, 30 ~ 100 Hz, tested by noise simulator

Dielectric Withstand 
Voltage

500 V AC > 1 min, tested between power terminals and ground

Insulation Resistance

5 M

 > at 500 V DC, tested between power terminals and ground

Ground

Grounding registance 100 

 or less. (class D)

Protection

IP 65F

50

(1

.9

7"

)

20

(0

.7

9"

)

-

+

2 4 V   D C

1 0 ( 0 . 3 9 " )

d )

1 0 ( 0 . 3 9 " )

h )

g )

f   )

e )

14

0(

5.

51

")

13

0(

5.

12

")

1 5 2 ( 5 . 9 8 " )

8 ( 0 . 3 1 " )

2 0 ( 0 . 7 9 " ) 2 0 ( 0 . 7 9 " )

8 ( 0 . 3 1 " )

5 ( 0 . 2 0 " )

i )

P O W E R

R

S

232C

R

S

422

5 7 ( 2 . 2 4 " )

5 ( 0 . 2 0 " )

a )

1 6 2 ( 6 . 3 8 " )

b )

c )

12

0(

4.

72

")

13

0(

5.

12

")

Summary of Contents for GOT-F900

Page 1: ...ng cable break when monitor is executed within the GOT communication between the GOT and programmable controller CPU is interrupted and it is impossible to operate switches or devices in the PLC through the GOT Communication and operation resumes when the GOT system is correctly configured DO NOT configure emergency stop or safety features to operate through the GOT and be sure that there is no ad...

Page 2: ...ng cable break when monitor is executed within the GOT communication between the GOT and programmable controller CPU is interrupted and it is impossible to operate switches or devices in the PLC through the GOT Communication and operation resumes when the GOT system is correctly configured DO NOT configure emergency stop or safety features to operate through the GOT and be sure that there is no ad...

Page 3: ...ng cable break when monitor is executed within the GOT communication between the GOT and programmable controller CPU is interrupted and it is impossible to operate switches or devices in the PLC through the GOT Communication and operation resumes when the GOT system is correctly configured DO NOT configure emergency stop or safety features to operate through the GOT and be sure that there is no ad...

Page 4: ...ect connection may result in unit failure or the GOT being burnt Attach a fuse of 2 A to the 24V DC power supply Perform Class D 100Ω or less grounding with an electric wire of at least 1 25 mm2 Never perform common grounding of the GOT and a strong power system Note Feed power to the GOT by an external power supply The service power supply of the programmable controller cannot be used Even if ins...

Page 5: ...ect connection may result in unit failure or the GOT being burnt Attach a fuse of 2 A to the 24V DC power supply Perform Class D 100Ω or less grounding with an electric wire of at least 1 25 mm2 Never perform common grounding of the GOT and a strong power system Note Feed power to the GOT by an external power supply The service power supply of the programmable controller cannot be used Even if ins...

Page 6: ...ect connection may result in unit failure or the GOT being burnt Attach a fuse of 2 A to the 24V DC power supply Perform Class D 100Ω or less grounding with an electric wire of at least 1 25 mm2 Never perform common grounding of the GOT and a strong power system Note Feed power to the GOT by an external power supply The service power supply of the programmable controller cannot be used Even if ins...

Page 7: ...ng cable break when monitor is executed within the GOT communication between the GOT and programmable controller CPU is interrupted and it is impossible to operate switches or devices in the PLC through the GOT Communication and operation resumes when the GOT system is correctly configured DO NOT configure emergency stop or safety features to operate through the GOT and be sure that there is no ad...

Page 8: ...ect connection may result in unit failure or the GOT being burnt Attach a fuse of 2 A to the 24V DC power supply Perform Class D 100Ω or less grounding with an electric wire of at least 1 25 mm2 Never perform common grounding of the GOT and a strong power system Note Feed power to the GOT by an external power supply The service power supply of the programmable controller cannot be used Even if ins...

Reviews: