3 Installation
3.1 Installation Arrangements
3.1
Installation Arrangements
The 32DP is connected to the extension port of an FX
3G
/FX
3GC*1
/FX
3U
/FX
3UC*1
/FX5U
*2
/FX5UC
*2
PLC or
extension unit/block (including special function unit/block) on the right side.
Since additional extension devices can be added on both the left and right-hand sides of the PLC, keep an
appropriate amount of space on both sides of the PLC when planning to add extension devices in the future.
For further details on installation arrangements, refer to the following manual.
→
FX
3G
PLC Hardware Edition
→
FX
3GC
PLC Hardware Edition
→
FX
3U
PLC Hardware Edition
→
FX
3UC
PLC Hardware Edition
→
MELSEC iQ-F FX5U User's Manual (Hardware)
→
MELSEC iQ-F FX5UC User's Manual (Hardware)
*1.
An FX
2NC
-CNV-IF or FX
3UC
-1PS-5V is necessary to connect to the 32DP with the FX
3GC
/FX
3UC
Series PLC.
However, the 32DP cannot be connected to the FX
3UC
-32MT-LT(-2).
*2.
An FX5-CNV-BUS or FX5-CNV-BUSC is necessary to connect to the 32DP with the FX5U/FX5UC
PLC.
Note
• Keep a space of 50 mm (1.97") or more between the 32DP and the other devices and cabinet.
Install the unit as far from high-voltage lines, high-voltage devices and power equipment as possible.
• To prevent the product’s temperature from rising, do not install the PLC on a floor, ceiling, or in the vertical
direction. Install it horizontally on a wall as shown below.
• Take care to position the 32DP and other peripheral devices for their extension ports and cables to be as
close to each other as possible.
FX
3G
/
FX
3U
/
FX
3UC
Series main unit
FX
3U
-32DP
≥
50mm (1.97")
A
A
A
A
A