FX2N-64CL-M CC-Link/LT Master Block
Handling Cautions 5
5-2
5.1
Installation
The FX
2N
-64CL-M can be attached via DIN rail or attached directly with screws.
The installation procedure in each case is described below.
5.1.1
Installation direction
•
Do not install the master block on floor surfaces, ceiling surfaces or in a horizontal direction.
If the master block is installed in such a way, its temperature may rise.
Install the master block vertically on wall surfaces as shown in the figure below.
•
Secure a space of 50 mm (1.96") or more between the master block and other equipment or
structures. Keep the master block off high voltage cables, high voltage equipment and
power equipment as much as possible.
5.1.2
DIN rail installation
Align the upper DIN rail installation groove in the module with the DIN rail 1), and press the
module in that position 2).
When removing the module, pull the installation hook downwards 3), then remove the module
4).
5.1.3
Direct installation
Fix the FX
2N
-64CL-M on to the panel surface by tightening M4 screws inserted in two (upper
and lower) mounting holes provided on the master block.
Install the FX
2N
-64CL-M and other units so that a clearance of 1 to 2 mm is assured among
each unit.
Applicable DIN rail
TH35-7.5Fe and TH35-7.5AI
Applicable screw
M4 height: 16mm(0.63") or more (Tightening torque range: 78 to 108 N
⋅
cm)
1)
Installation
Removal
2)
3)
4)
Summary of Contents for FX2N-64CL-M
Page 1: ...USER S MANUAL Detailed Volume FX2N 64CL M CC Link LT Master Block ...
Page 4: ...FX2N 64CL M CC Link LT Master Block ii ...
Page 6: ...FX2N 64CL M CC Link LT Master Block iv ...
Page 12: ...FX2N 64CL M CC Link LT Master Block x ...
Page 26: ...FX2N 64CL M CC Link LT Master Block System Startup Procedure 3 3 2 ...
Page 50: ...FX2N 64CL M CC Link LT Master Block Various Modes 7 7 2 ...
Page 74: ...FX2N 64CL M CC Link LT Master Block Model Assignment of Buffer Memory 10 10 14 ...
Page 93: ......