10 Input Wiring Procedures (Input Interruption and Pulse Catch)
10.3 100V AC Input Type
10.3.2 Handling of 100V AC Input
1. Input terminal
When voltage of 100 to 120V AC is applied between the input
terminal and COM terminal, the input terminal is turned on.
The input display LED is lit.
Do not connect the COM terminal of an AC input type main
unit and input/output powered extension unit/block with the
COM terminal of a DC system.
2. Input circuit
The primary input circuit and the secondary input circuit are
insulated with a photocoupler.
There is a delay of approx. 25 to 30ms in response to input
switching from ON to OFF and from OFF to ON.
3. Input sensitivity
The input current and input sensitivity of these PLCs are
shown in the following table.
4. Cautions on use
The response time of the AC input type is slower than that of the DC input type.
The applications shown below are not supported.
Input
Specifications
Input voltage
100 to 120V AC +10%, -15% 50/60Hz
Input current
6.2 mA/110V 60Hz
4.7 mA/100V 50Hz
Percentage of simultaneous power-on:
70% or less
Input
sensitivity
ON
3.8 mA or more
OFF
1.7 mA or less
Unsupported Applications
High-speed
processing
High-speed counter, input interruption, pulse catch, speed detection (SPD) instruction
Time division input
Input matrix (MTR) instruction, hexadecimal input (HKY) instruction, digital switch (DSW)
instruction, arrow switch (ARWS) instruction
Other
Refresh and filter adjust (REFF) instruction, ten key input (TKY) instruction, absolute current
value read (ABS) instruction
X001
X007
*
N
L
100 to 240V AC
Fuse
Fuse
COM
X000
100 to 120V AC
* Input impedance