5. Specifications
Caution
•
Do not touch the terminals while power is ON.
Electric shock is possible.
•
Cleaning and additional tightening of the terminal should only be done after turning OFF
the power supply.
Electric shock is possible while the power is ON.
•
For repair please contact a service representative. Incorrect repair can cause malfunction
or electric shock.
•
Install and uninstall FX
1N
-4EX-BD after turning OFF the power supply. Installing and
uninstalling while the power supply is ON may cause malfunction.
•
Treat as industrial waste when disposing of the product.
5.1 Environmental specifications
The environmental specifications are equivalent to those of the PLC main unit. (Refer to the manual of the
PLC main unit.)
5.2 Power supply specifications
5.3 INPUT specifications
Item
Specification
Consumption current
5V DC
Supply by PLC.
24V DC
25mA or less. Supply from external power supply.
Item
Specification
Input signal voltage
24V DC +20% -15%
Input signal current
About 5mA/24V DC
Input ON current
3.5mA or more
Input OFF current
1.5mA or less
Input response time
About 10mS
Input signal form
Without voltage contact or opening collector Transistor
Circuit insulation
Photo coupler
Operation display
LED lighting when photo coupler is driven
Manual number : JY992D95001
Manual revision : A
Date
:
May 2001