Mitsubishi FX1N-4EX-BD User Manual Download Page 6

HEAD OFFICE

: MITSUBISHI DENKI BLDG MARUNOUTI TOKYO 100-8310

TELEX : J24532 CABLE MELCO TOKYO

HIMEJI WORKS : 840, CHIYODA CHO, HIMEJI, JAPAN

5. Specifications

Caution

Do not touch the terminals while power is ON.
Electric shock is possible. 

Cleaning and additional tightening of the terminal should only be done after turning OFF
the power supply. 
Electric shock is possible while the power is ON. 

For repair please contact a service representative. Incorrect repair can cause malfunction
or electric shock.

Install and uninstall FX

1N

-4EX-BD after turning OFF the power supply. Installing and

uninstalling while the power supply is ON may cause malfunction. 

Treat as industrial waste when disposing of the product. 

5.1 Environmental specifications

The environmental specifications are equivalent to those of the PLC main unit. (Refer to the manual of the
PLC main unit.)

5.2 Power supply specifications

5.3 INPUT specifications

Item

Specification

Consumption current

5V DC

Supply by PLC.

24V DC

25mA or less. Supply from external power supply.

Item

Specification

Input signal voltage

24V DC +20% -15%

Input signal current

About 5mA/24V DC

Input ON current

3.5mA or more

Input OFF current

1.5mA or less

Input response time

About 10mS

Input signal form

Without voltage contact or opening collector Transistor 

Circuit insulation

Photo coupler

Operation display

LED lighting when photo coupler is driven

Manual number : JY992D95001

Manual revision : A

Date

:

 

May 2001

Reviews: