Object Object
type
Instance
number
Management item
Note
Prohibition of local operation
(filter reset)
Binary Value
xxxx15 Inactive:
Permit
Active:
Prohibit
Prohibition of local operation
(Set Temp.)
Binary Value
xxxx16 Inactive:
Permit
Active:
Prohibit
*3)
Communication State
Binary Input
xxxx20
Inactive:
Normal
Active:
Abnormalities
System Forced Off
Binary Value
xx9921 Inactive:
Released
Active:
Effective
Air direction (setup)
Multi-State Output
xxxx22
01: Horizontal
02: Down 60%
03: Down 80%
04: Down100%
05: Swing
*3)
Air direction (state)
Multi-State Input
xxxx23
01: Horizontal
02: Down 60%
03: Down 80%
04: Down100%
05: Swing
*3)
Notification Class
Notification Class
000003
Setting change of an instance
number is possible.
Device
Device
000003
Setting change of an instance
number is possible.
*1) It can use, if dry operation use is set up.
*2) It can use, if use of Mid1/Mid2 is set up.
*3) The group of LC serves as an item with an invalid attribute.
*4) As for the operation mode of the group of LC, an attribute serves as ventilation fixation.