2.2 Performance Specifications
Table 2.2 Performance specifications
Item
Specifications
RS-232
-
Interface
RS-232 compliant (D-Sub 9P)
Communication
method
Full-duplex communication method
Synchronization
method
Asynchronous method
Transmission speed
300, 600, 1200, 2400, 4800, 9600, 19200, 38400, 57600
*1
,
115200
*1
(bps)
(Select with RS-232 transmission setting switches.)
Transmission
distance
Up to 15m
Data
format
Start bit
1
Data bit
7/8
Parity bit
1 (Vertical parity)/None
Stop bit
1/2
Error
detection
Parity
check
Checked (even/odd)/Not checked
Communication
control (Flow control)
DTR/DSR (ER/DR) control
DC1/DC3 control
OS reception area
5120 bytes
CC-Link
-
CC-Link station type
Intelligent device station
Connection cable
CC-Link dedicated cable/CC-Link high-performance cable/CC-Link
Ver.1.10-compatible cable
*2
No. of occupied
stations
1 station (RX/RY: 32 points each, RWw/RWr: 4 points each)
No. of writes to
E
2
PROM
Up to 100,000 times
Withstand voltage
One minute at 500V AC between all external DC terminals and ground
Insulation resistance
500V DC between all external DC terminals and ground, 10M or
more with insulation resistance tester
Noise immunity
DC type noise voltage: 500Vp-p,
tested by noise simulator of noise width of 1 s and noise frequency of
25 to 60Hz
Module fixing screw
M4 0.7mm 16mm or larger
DIN-rail mounting is also possible.
Applicable DIN rail
TH35-7.5Fe, TH35-7.5Al, TH35-15Fe (Compliant with IEC 60715)
External power supply
24V DC (20.4 to 26.4V DC, the ripple ratio is 5% or less)
Current consumption: 0.11A (TYP. 24V DC)
Allowable momentary
power failure time
1ms
External dimensions
80(H) 170(W) 47(D) [mm]
Weight
0.40kg