8 -
21
8.
LOADING AND INSTALLATION
8.7.2
Wiring to module terminals
This section explains the wiring of power cables and ground wires to the main and
extension bases.
POINT
(1) Use the thickest possible (max. 2 mm
2
(14 AWG)) wires for the 100/200 VAC
and 24 VDC power cables. Be sure to twist these wires starting at the
connection terminals. For wiring a terminal block, be sure to use a solderless
terminal. To prevent short-circuit due to loosening screws, use the solderless
terminals with insulation sleeves of 0.8 mm (0.03 inch) or less thick. The
number of the solderless terminals to be connected for one terminal block are
limited to 2
(2) Be sure to ground the LG and FG terminals. Failure to do so may cause the
programmable controller to be susceptible to noise. Note that LG terminals
include the potential as half as that of input voltage; you might get an electric
shock when you touch them.
(3) A1S61PN and A1S62PN do not need to be switched as the are 100 to
240VAC wide-range.
Extension base unit (A1S68B)
Extension base unit (A1S58B)
AC
100/110VAC
24VDC
AC
DC
A1S61PN
CPU
NC
NC
(FG)
(LG)
INPUT
100-240VAC
I/O
I/O
FG
AC
100/110VAC
24VDC
24VDC
AC
DC
A1S62PN
CPU
A1S62PN
I/O
100/240VAC
+24V
24G
(FG)
(LG)
INPUT
100-240VAC
+24V
24G
(FG)
(LG)
INPUT
100-240VAC
Main base unit (A1S38B)
Fuse
Fuse
Connect to the 24VDC
terminals of an I/O
module that requires
24VDC internally.
Extension cable
Extension cable
Ground
Grounding wire
Ground
Grounding wire
200/240VAC
200/240VAC
Main base unit (A1S38B)
Connect to the 24VDC
terminals of an I/O
module that requires
24VDC internally.
Terminal block
Solderless terminals
with insulation sleeves