23
●
Air-conditioner Cell Configuration File Upload/Download screen
This screen is used to download the Air-conditioner Cell Configuration information which was set on the
Air-conditioner Cell Configuration screen to a computer, or upload an Air-conditioner Cell Configuration
File from a computer for control and monitoring to this gateway.
An Air-conditioner Cell Configuration file is a CSV file or XML file containing a list of the SL system No., SL
address, Accounting Type, Capacity, Air-conditioner Cell name, Description, meter information, and
Calculation interval of each air conditioner in Air-conditioner Cells indexed by the Air-conditioner Cell No.
When either the CSV or XML format is selected and the file is exported, the Air-conditioner Cell
Configuration File "PACinfo256.csv" or "PACinfo256.xml" will be saved to the computer. It is possible to
edit files with spreadsheet software, etc.
If a CSV file (PACinfo256.csv) or XML file (PACinfo256.xml) on a computer is uploaded to this gateway,
the contents of this file will be used for the Air-conditioner Cell Configuration screen.
<Examples of Air-conditioner Cell Configuration>
CELL_
NO
PLACE
PLACE_
SHORT
SL_LINE
SL_
ADDRESS
KAKIN_
TYPE
ABILITY P1 T1 C1
・・・
P8 T8 C8 INTERVAL
C000
This room
is Cell 000.
Room
000
S1 U000
MULTI1
5.6
1
C001
This room
is Cell 001.
Room
001
S1 U001
MULTI1
7.1
1
C001
This room
is Cell 001.
Room
001
S1 U002
RUN/
STOP
7.1
1
C001
This room
is Cell 001.
Room
001
S1 U004
RUN/
STOP
14
1
・・・
・・・
・・・
・・・
・・・
・・・
・・・
・・・
・・・
・・・
・・・
・・・
・・・
・・・
・・・
<How to interpret the above table.>
・
Items are as follows.
- Air-conditioner Cell Number
: CELL_NO
- Description
: PLACE
- Air-conditioner Cell Name
: PLACE_SHORT
- SL System Number
: SL_LINE
- SL Address
: SL_ADDRESS
- Accounting Type
: KAKIN_TYPE
- Capacity[kW]
: ABILITY
- Meter Connection Information
: P1
~
P8
- Meter Information
・
WATT/GAS
: T1
~
T8
・
Unit Quantity Per Pulse
: C1
~
C8
- Calculation Interval
: INTERVAL
・
The air conditioner with the SL address U000 in the Superlink system SL1 is set in Air-conditioner Cell
No. C000.
・
Air conditioners with SL address U001, U002 and U004, respectively, in the Superlink system SL1, are
set in Air-conditioner Cell C001, and these three air conditioners are grouped together as a single
logical object. The air conditioner with the lower SL address becomes the representative unit in the
Air-conditioner Cell, and the Air-conditioner Cell name and Description are set.
・
The address U003 is omitted, but this indicates that air conditioner U003 is not currently connected.