-
-
'15 • SRK-T-175
Necessary tools for the installation work
1
2
3
4
5
6
7
8
9
10
11
12
13
1
1
1
1
1
1
Q’ty
Locally procured parts
Sealing plate
Sleeve
Inclination plate
Putty
Drain hose (extension hose)
Piping cover
(for insulation of connection piping)
Plus headed driver
Knife
Saw
Tape measure
Hammer
Spanner wrench
Torque wrench
Hole core drill (65mm in diameter)
Wrench key (Hexagon) [4m/m]
Flaring tool set
Gas leak detector
Pipe bender
Gauge for projection adjustment
Used when flare is made by using
conventional flare tool
(
)
( )
14.0 ~ 82.0N·m
(1.4 ~ 8.2kgf·m)
(
Designed specifically
for R410A
)
BEFORE INSTALLATION
○
Before installation check that the power source matches the
air-conditioner.
R410A REFRIGERANT USED
WALL TYPE AIR-CONDITIONER
INSTALLATION MANUAL FOR INDOOR UNIT
RLD012A001
1
1
1
10
2
2
2
Q’ty
Standard accessories (Installation kit)
Accessories for indoor unit
Installation board
(Attached to the rear of the indoor unit)
Wireless remote control
Remote control holder
Battery [R03 (AAA, Micro) 1.5V]
Air-cleaning filters
2
1
Insulation (#486 50 x 100 t3)
Filter holders
Tapping screws
(for installation board ø4 X 25mm)
Wood screws
(for remote control holder ø3.5 X 16mm)
1
2
3
4
5
6
7
8
9
(
)
Designed specifically
for R410A
INSTALLATION SPACE (INDOOR UNIT)
(FRONT VIEW)
Relation between setting plate and indoor unit
5 cm minimum
from the wall
15 cm minimum
from the wall
Installation board
Sleeve (sold separately)
10 cm minimum from the ceiling
[Drain hose changing procedures]
1. Remove the drain hose
2. Remove the drain cap.
○
Remove it with hand or pliers.
○
Remove the screw and drain hose,
making it rotate.
3. Insert the drain cap.
4. Connect the drain hose.
○
Insert the drain cap which was removed
at procedure “2” securely using a
hexagonal wrench etc.
Note: Be careful that If it is not inserted
securely, water leakage may occur.
○
Insert the drain hose securely, making
rotate. And install the screw.
Note: Be careful that If it is not inserted
securely, water leakage may occur.
CAUTION
Completely seal the hole on
the wall with putty. Otherwise,
furniture, or other, may be
wetted by leaked water or
dewing.
putty
putty
Indoor side
Outdoor side
Piping in the left direction
Piping in the right rear direction
Piping in the left rear direction
Piping in the right direction
Piping is possible in the rear, left, left rear, left downward, right or downward direction.
Right
Rear
Downward
Left
rear
Left downward
Left
Installing the support of piping
In case of piping in the right rear direction
Sufficient care must be taken not to damage
the panel when connecting pipes.
[Top view]
When drilling the wall that contains a metal lath, wire lath or metal plate, be sure to use pipe hole sleeve sold separately.
• Matters of special notice when piping from left or central/rear of the unit.
Left-hand-side piping
Right-hand-side piping
Drilling of hole and fixture of sleeve (Locally procured parts)
Shaping of pipings
Taping of the exterior
Pipings
Drain hose
Top
Thickness of the wall + 1.5cm
5
ø65
Indoor side
Outdoor side
Indoor side
Outdoor side
Installed state
Turn to
tighten
b
b
c
a
○
In case of rear piping draw out, cut off the lower
and the right side portions of the sleeve collar.
○
Drill a hole with whole core drill.
○
Hold the bottom of the
piping and fix direction
before stretching it and
shaping it.
○
Tape only the portion that
goes through the wall.
○
Always tape the wiring
with the piping.
180 cm minimum from the floor
screw
cap
(Unit : mm)
SELECTION OF INSTALLATION LOCATION
INSTALLATION OF INDOOR UNIT
Indoor unit
(Install at location that meets the following conditions, after getting approval from the customer)
○
Where there is no obstructions to the air flow and where the cooled and heated air can be evenly distributed.
○
A solid place where the unit or the wall will not vibrate.
○
A place where there will be enough space for servicing. (Where space mentioned below can be secured)
○
Where wiring and the piping work will be easy to conduct.
○
The place where receiving part is not exposed to the direct rays of the sun or the strong rays of the street lighting.
○
A place where it can be easily drained.
○
A place separated at least 1m away from the television or the radio. (To prevent interference to images and sounds.)
○
Places where this unit is not affected by the high frequency equipment or electric equipment.
○
Avoid installing this unit in place where there is much oil mist.
○
Places where there is no electric equipment or household under the installing unit.
○
Install the indoor unit on the wall where the height from the floor to the bottom of the unit is more than 1.8m.
Wireless remote control
○
A place where the air-conditioner can be received the signal surely during operating the wireless remote control.
○
Places where there is no affected by the TV and radio etc.
○
Do not place where exposed to direct sunlight or near heat devices such as a stove.
Installation of Installation board
Fixing on concrete wall
Use of nut anchor
Bolt
(M6 12)
Standard
hole
Installation
sample
Indoor unit
Obstacle such
as curtain
Be sure that the flap
of outlet should not
touch any obstacles.
for service
Indoor unit
768
157
214.5
214.5
883
157
53.5
77
150
50
Piping for Liquid 780
Installation board
60
470
363.5
363.5
568.5
568.5
Space
for service
Space
and nut anchor
For bolt anchor
Piping hole (ø65)
Drain hose 759 (ø16)
Piping for Gas
715 (SRK24/71/80/92/100, DXK24/28/32)
709 (SRK63, DXK21)
○
Adjustment of the installation board in the horizontal direction is
to be conducted with eight screws in a temporary tightened state.
○
Adjust so the board will be level by turning the board with the
standard hole as the center.
13
cm
Wireless remote control
Remote control holder
Wood screws
Look for the inside wall structures (Intermediate support or pillar
and firmly install the unit after level surface has been checked.)
768
410
Mating mark for
level surface
WARNING
• Installation must be carried out by the qualified installer.
If you install the system by yourself, it may cause serious trouble such as
water leaks, electric shocks, fire and personal injury, as a result of a
system malfunction. Do not carry out the installation and maintenance
work except the by qualified installer.
• Install the system in full accordance with the installation manual.
Incorrect installation may cause bursts, personal injury, water leaks,
electric shocks and fire.
• Be sure to use only for household and residence.
If this appliance is installed in inferior environment such as machine shop
and etc., it can cause malfunction.
• Use the original accessories and the specified components for
installation.
If parts other than those prescribed by us are used, It may cause water
leaks, electric shocks, fire and personal injury.
• Install the unit in a location with good support.
Unsuitable installation locations can cause the unit to fall resulting in
material damage and personal injury.
• Ventilate the working area well in the event of refrigerant leakage
during installation.
If the refrigerant comes into contact with naked flames, poisonous gas is
produced.
• When installing in small rooms, take prevention measures not to
exceed the density limit of refrigerant in the event of leakage,
referred by the formula (accordance with ISO5149).
If the density of refrigerant exceeds the limit, consult the dealer and
install the ventilation system, otherwise lack of oxygen can occur, which
can cause serious accident.
• After completing installation, check that no refrigerant leaks from
the system.
If refrigerant leaks into the room and comes into contact with an oven or
other hot surface, poisonous gas is produced.
• Use the prescribed pipes, flare nuts and tools for R410A.
Using existing parts (for R22 or R407C) can cause the unit failure and
serious accidents due to burst of the refrigerant circuit.
•
Tighten the flare nut by torque wrench with specified method.
If the flare nuts were tightened with excess torque, this may cause burst
and refrigerant leakage after a long period.
• The electrical installation must be carried out by the qualified
electrician in accordance with “the norm for electrical work” and
“national wiring regulation”, and the system must be connected to
the dedicated circuit.
Power source with insufficient capacity and incorrect function done by
improper work can cause electric shocks and fire.
• Be sure to shut off the power before starting electrical work.
Failure to shut off the power can cause electric shocks, unit failure or
incorrect function of equipment.
• Be sure to use the cables conformed to safety standard and cable
ampacity for power distribution work.
Unconformable cables can cause electric leak, anomalous heat
production or fire.
• This appliance must be connected to main power source by means
of a circuit breaker or switch [fuse Model 63(21):16A, Model 71(24),
80(28), 92, 100:20A] with a contact separation of at least 3mm.
• When plugging this appliance, a plug conforming to the norm
IEC60884-1 must be used.
• Use the prescribed cables for electrical connection, tighten the
cables securely in terminal block and relieve the cables correctly to
prevent overloading the terminal blocks.
Loose connections or cable mountings can cause anomalous heat
production or fire.
• Arrange the wiring in the control box so that it cannot be pushed up
further into the box. Install the service panel correctly.
Incorrect installation may result in overheating and fire.
• Be sure to switch off the power source in the event of installation,
inspection or servicing.
If the power source is not shut off, there is a risk of electric shocks, unit
failure or personal injury due to the unexpected start of fan.
• Be sure to wear protective goggles and gloves while at work.
• Earth leakage breaker must be installed.
If the earth leakage breaker is not installed, it can cause electric shocks.
CAUTION
•
Use the circuit breaker of correct capacity. Circuit breaker should be able to
disconnect all poles under over current.
Using the incorrect one could cause the system failure and fire.
• Install isolator or disconnect switch on the power source wiring in
accordance with the local codes and regulations.
The isolator should be locked in OFF state in accordance with EN60204-1.
•
Be sure to install indoor unit properly according to instruction manual so
that drainage can run off smoothly.
Improper installation of indoor unit can cause dropping water into the room and
damaging personal property.
• Install the drainage pipe to run off drainage securely according to the
installation manual.
Incorrect installation of the drainage pipe can cause dropping water into the room
and damaging personal property.
• Be sure to install the drainage pipe with descending slope of 1/100 or more,
and not to make traps and air-bleedings.
Check if the drainage runs off securely during commissioning and ensure the
space for inspection and maintenance.
•
After maintenance, all wiring, wiring ties and the like, should be returned to
their original state and wiring route, and the necessary clearance from all
metal parts should be secured.
• Secure a space for installation, inspection and maintenance specified in the
manual.
Insufficient space can result in accident such as personal injury due to falling
from the installation place.
• Take care when carrying the unit by hand.
If the unit weights more than 20kg, it must be carried by two or more persons. Do
not carry by the plastic straps, always use the carry handle when carrying the unit
by hand. Use gloves to minimize the risk of cuts by the aluminum fins.
•
Dispose of any packing materials correctly.
Any remaining packing materials can cause personal injury as it contains nails
and wood. And to avoid danger of suffocation, be sure to keep the plastic
wrapper away from children and to dispose after tear it up.
• For installation work, be careful not to get injured with the heat exchanger,
piping flare portion or screws etc.
• Be sure to insulate the refrigerant pipes so as not to condense the ambient
air moisture on them.
Insufficient insulation can cause condensation, which can lead to moisture
damage on the ceiling, floor, furniture and any other valuables.
• When perform the air-conditioner operation (cooling or dehumidifying
operation) in which ventilator is installed in the room. In this case, using the
air-conditioner in parallel with the ventilator, there is the possibility that
drain water may backflow in accordance with the room lapse into the
negative pressure status. Therefore, set up the opening port such as
incorporate the air into the room that may appropriate to ventilation (For
example; Open the door a little). In addition, just as above, so set up the
opening port if the room lapse into negative pressure status due to register
of the wind for the high rise apartment etc.
• Be sure to perform air tightness test by pressurizing with nitrogen gas after
completed refrigerant piping work.
If the density of refrigerant exceeds the limit in the event of refrigerant leakage in
the small room, lack of oxygen can occur, which can cause serious accidents.
• Do not install the unit in the locations listed below.
• Locations where carbon fiber, metal powder or any powder is floating.
• Locations where any substances that can affect the unit such as sulphide
gas, chloride gas, acid and alkaline can occur.
• Vehicles and ships.
• Locations where cosmetic or special sprays are often used.
• Locations with direct exposure of oil mist and steam such as kitchen and
machine plant.
• Locations where any machines which generate high frequency harmonics
are used.
• Locations with salty atmospheres such as coastlines.
• Locations with heavy snow (If installed, be sure to provide base flame and
snow hood mentioned in the manual).
• Locations where the unit is exposed to chimney smoke.
• Locations at high altitude (more than 1000m high).
• Locations with ammonic atmospheres (e.g. organic fertilizer).
• Locations with calcium chloride (e.g. snow melting agent).
• Locations where heat radiation from other heat source can affect the unit.
• Locations without good air circulation.
• Locations with any obstacles which can prevent inlet and outlet air of the unit.
• Locations where short circuit of air can occur (in case of multiple units
installation).
• Locations where strong air blows against the air outlet of outdoor unit.
• Locations where something located above the unit could fall.
It can cause remarkable decrease in performance, corrosion and damage of
components, malfunction and fire.
• Do not install the indoor unit in the locations listed below (Be sure to
install the indoor unit according to the installation manual for each
model because each indoor unit has each limitation).
• Locations with any obstacles which can prevent inlet and outlet air of the unit.
• Locations where vibration can be amplified due to insufficient strength of structure.
• Locations where the infrared receiver is exposed to the direct sunlight or
the strong light beam (in case of the infrared specification unit).
• Locations where an equipment affected by high harmonics is placed (TV
set or radio receiver is placed within 1m).
• Locations where drainage cannot run off safely.
It can affect performance or function and etc.
• Do not install the unit near the location where leakage of
combustible gases can occur.
If leaked gases accumulate around the unit, it can cause fire.
• Do not install the unit where corrosive gas (such as sulfurous acid
gas etc.) or combustible gas (such as thinner and petroleum gases)
can accumulate or collect, or where volatile combustible substances
are handled.
Corrosive gas can cause corrosion of heat exchanger, breakage of plastic
parts and etc. And combustible gas can cause fire.
• Do not use the indoor unit at the place where water splashes may
occur such as in laundries.
Since the indoor unit is not waterproof, it can cause electric shocks and fire.
• Do not install nor use the system close to the equipment that
generates electromagnetic fields or high frequency harmonics.
Equipment such as inverters, standby generators, medical high frequency
equipments and telecommunication equipments can affect the system, and
cause malfunctions and breakdowns. The system can also affect medical
equipment and telecommunication equipment, and obstruct its function or
cause jamming.
• Do not place any variables which will be damaged by getting wet
under the indoor unit.
When the relative humidity is higher than 80% or drainage pipe is clogged,
condensation or drainage water can drop and it can cause the damage of
valuables.
• Do not install the remote control at the direct sunlight.
It can cause malfunction or deformation of the remote control.
• Do not use the unit for special purposes such as storing foods,
cooling precision instruments and preservation of animals, plants
or art.
It can cause the damage of the items.
• Do not use any materials other than a fuse with the correct rating in
the location where fuses are to be used.
Connecting the circuit with copper wire or other metal thread can cause unit
failure and fire.
• Do not touch any buttons with wet hands.
It can cause electric shocks.
• Do not touch any refrigerant pipes with your hands when the system
is in operation.
During operation the refrigerant pipes become extremely hot or extremely cold
depending the operating condition, and it can cause burn injury or frost injury.
• Do not wash the inside of the air-conditioner.
Water leakage and permanent damage may result.
Electrical hazard exists.
• Carry out the electrical work for ground lead with care.
Do not connect the ground lead to the gas line, water line, lightning conductor or telephone line’s ground lead. Incorrect grounding can cause unit
faults such as electric shocks due to short-circuiting.
• Do not put the drainage pipe directly into drainage channels where
poisonous gases such as sulphide gas can occur.
Poisonous gases will flow into the room through drainage pipe and
seriously affect the user’s health and safety. This can also cause the
corrosion of the indoor unit and a resultant unit failure or refrigerant leak.
• Ensure that no air enters in the refrigerant circuit when the unit is
installed and removed.
If air enters in the refrigerant circuit, the pressure in the refrigerant circuit
becomes too high, which can cause burst and personal injury.
• Do not process or splice the power cord, or share the socket with
other power plugs.
This may cause fire or electric shock due to defecting contact, defecting
insulation and over-current etc.
• Do not bundle or wind or process the power cord. Do not deform
the power cord by treading it.
This may cause fire or heating.
• Do not vent R410A into the atmosphere : R410A is a fluorinated
greenhouse gas, covered by the Kyoto Protocol with Groval
Warming Potential (GWP)=1975.
• Do not run the unit with removed panels or protections.
Touching rotating equipments, hot surfaces or high voltage parts can
cause personal injury due to entrapment, burn or electric shocks.
• Do not perform any change of protective device itself or its setup
condition.
The forced operation by short-circuiting protective device of pressure
switch and temperature controller or the use of non specified component
can cause fire or burst.
SAFETY PRECAUTIONS
• Before installation, read the “SAFETY PRECAUTIONS” carefully and strictly
follow it during the installation work in order to protect yourself.
• The precautionary items mentioned below are distinguished into two levels,
and .
: Wrong installation would cause serious consequences such
as injuries or death.
: Wrong installation might cause serious consequences
depending on circumstances.
Both mention the important items to protect your health and safety so strictly
follow them by any means.
• Be sure to confirm no anomaly on the equipment by commissioning after completed
installation and explain the operating methods as well as the maintenance methods
of this equipment to the user according to the owner’s manual.
• Keep the installation manual together with owner’s manual at a place where
any user can read at any time. Moreover if necessary, ask to hand them to a
new user.
• Before starting the installation work, proper precautions (using suitable
protective clothing, groves etc.) should be taken by qualified installer.
• Pay attention not to fall down the tools, etc. when installing the unit at the
high position.
• If unusual noise can be heard during operation, consult the dealer.
• The meanings of “Marks” used here are shown as follows:
Never do it under any
circumstances.
Always do it according to the
instruction.
CAUTION
WARNING
CAUTION
WARNING
• This installation manual illustrates the method of installing an indoor unit.
• For electrical wiring work, see instructions set out on the backside.
• For outdoor unit installation and refrigerant piping, refer to page 26.
• A wired remote control unit is supplied separately as an option part.
• While installing the unit, be sure to check the selection of installation place,
power source specifications, usage limitation (piping length, height
differences between indoor and outdoor units, power source voltage etc.)
and installation spaces.
8. APPLICATION DATA
(1) Installation of indoor unit