17
-
(12) Dew condensation prevention control for cooling operation
This prevents dew condensation, in the indoor unit, from occurring.
(a)
Operating condition:
when 52C is kept ON for 30 min. after the unit starts operation.
(b)
Operation content:
forces the indoor fan to change from Speed 1 to Speed 2.
(c)
Resetting condition:
When 52C is off, or when dew condensation prevention control has been operating continuously for
30 minutes.
(13) Frost prevention for indoor heat exchanger
[Preventing frost accumulation on the indoor heat exchanger]
During the Cooling or Dry operation in low room air temp. condition, evaporating temperature will decrease and consequently
indoor heat exchanger sometimes gets clogged with frost (or ice).
In order to prevent this trouble, compressor is stopped by under mentioned condition by indoor heat exchanger thermistor (Th2)
and timer (built into micro computer circuit) functions.
Also indoor fan is changed over to Lo speed.
CM, FM
O
stoppage condition
1
Temperature of heat exchanger is
0˚C or lower.
2
As least 10 minutes has passed
since the compressor started.
Indoor heat exchanger
temperature (˚C)
CM, FM
O
re-starting condition
1
Temperature of heat exchanger is
7˚C or higher.
2
As least 3 minutes has passed since
the compressor stopped.
Set fan
speed
(14) Microcomputer Controlled Timely Defrosting Operation
S
SRK28HJ
(a)
Defrost Start
Changes in the difference in temperature between the intake air temperature and the indoor heat exchanger temperature
causes frost to build up, at which time defrosting begins. However, defrosting will not occur when the total compressor
operation time or time after defrosting has ended is 40 minutes.
(b)
Defrost End
After defrosting has continued for 3 minutes or 7 minutes (when thermal is off before defrosting), defrosting will end and
heating will begin again.
Device operation during defrosting
#
OFF
ON
OFF
ON
OFF
ON
OFF
ON
In
d
o
o
r
Outdoor
Indoor Fan
Operation Lamp
52 C
(Compressor)
52 X
4
(Four Way Valve)
52 X
5
(Outdoor Fan)
seconds
1 minute
2 minutes
Start Defrosting
End Defrosting
Hot
Keep
Hot
Keep
Lit
Flashing
3 minutes or 7 minutes