28
-
RUN lamp
1 time flash
2 time flash
6 time flash
TIMER lamp
1 time flash
2 time flash
4 time flash
Outdoor unit LED
OFF
OFF
OFF
Heat exchanger thermistor error
Room temperature thermistor error
Indoor fan motor error
¡
Broken heat exchanger thermistor wire, connector
poor connection
¡
Broken room temperature thermistor wire,
connector poor connection
¡
Defective fan motor, connector poor connection
Trouble
Cause
OFF
OFF
OFF
Outdoor temperature thermistor
error
Outdoor unit heat exchanger
thermistor error
Discharge pipe thermistor error
¡
Broken outdoor thermistor wire, connector poor
connection
¡
Broken heat exchanger thermistor wire, connector
poor connection
¡
Broken discharge pipe thermistor wire, connector
poor contact
1 time flash
2 time flash
5 time flash
6 time flash
1 time flash
2 time flash
5 time flash
6 time flash
Current cut
Outdoor unit error
Compressor overheat
Serial signal transmission error
¡
Compressor faulty
¡
Overload operation (51C operation)
¡
Gas shortage.
¡
Defective discharge pipe thermistor.
¡
Compressor lock.
¡
Closed service valve.
¡
Broken signal wire.
¡
Defective indoor/outdoor unit PCB.
(3)
Inspection procedures corresponding to detail of trouble
Thermistor error
[Broken thermistor wire,
connector poor connection]
(Shortcircuit)
(Broken wire)
Is connector connection good?
YES
YES
NO
NO
Replace PCB.
Correct connection.
Replace thermistor.
Is thermistor resistance value good?
◆
Thermistor temperature characteristics
(Room temp., indoor unit heat exchanger
temp., outdoor unit heat exchanger
temp., outdoor temp.)
Temperature (˚C)
Resistance (k
Ω
)
30
25
20
15
10
5
30
20
10
40
50
60
70
0
–10
Temperature (˚C)
Resistance (k
Ω
)
Temperature (˚C)
Resistance (k
Ω
)
0
164
70
8.7
5
127
75
7.3
10
99
80
6.2
15
78
85
5.3
20
62
90
4.5
25
50
95
3.9
30
40
100
3.3
35
32
105
2.9
40
26
110
2.5
45
21
115
2.2
50
17
120
1.9
55
14
125
1.6
60
12
130
1.4
65
10
135
1.3
◆
Discharge pipe thermistor temperature characteristics
(2)
Self diagnosis display on indoor unit
TIMER lamp
ON
RUN lamp
keeps flashing
RUN lamp