General Purpose Interface  for  SC-GIFN-E(Optional Parts) 

 Be sure to read this manual before starting installation, and follow the instructions. 

 Refer also to the instruction manuals for the indoor unit and outdoor unit. 

 

S a f e t y   P r e c a u t i o n s  

 

Be sure to read this section thoroughly and strictly follow the installation instructions. 

Precautions have been classified under ” 

 

  WARNING” and “      CAUTION.” Items that have a high risk of leading to serious consequences, such as death and injury, 

when installation is performed improperly are listed in the “      WARNING” section. Note that it is possible that the items listed in the “      CAUTION” section may also   

lead to serious consequences depending on conditions. Items in both sections cover important safety information. Please abide by them. 

After installation, perform a test run to check that there are no abnormalities. Then, explain the operating procedure to the customer according to the instruction

 

manual. Ask 

the customer to save this instruction manual. 

To perform maintenance on the general purpose machine, turn off the power in advance.

 

 
 

 
 

 

 
 
 
 
 
 
 
 
 
 
 
 
 
 

1 Applicable Models 

General purpose equipment such as PAC for industry, pumps, and fans 

2 Accessories (Check the following accessories.) 

Interface, four attachment screws (W101D45×016), and instruction manual 

3 Feature 

You can start/stop and monitor (operation and error display) the applicable models indicated in 1 from the   

centralised controller. 

4 Model 

SC-GIFN-E , AC220V-240V power supply 

5 Control Switch 

You can use SW3 and SW4 on the interface PWB Assy to change the following control parameters. 
Change them at the site if necessary. We recommend that you use a precision screwdriver to change the settings.

 

Switch Symbol

Setting

Control detail

ON

Old superlink connection(*1)

OFF(factory setting)

New superlink connection

ON

Hundred's place[1]

OFF(factory setting)

Hundred's place[0]

ON

Pulse output       (*2)

OFF(factory setting)

Level output

ON
OFF(factory setting)

Reserved

SW3

1

2

SW4

1

2

 

(*1) If the network you are connecting to is the old superlink, you must change this setting. 
Whether the actual network is the new superlink or the old superlink depends on the type of indoor units, outdoor units, etc. Check with the agent or dealer. 
(*2) For details on switching the level/pulse output, see6 

WARNNG 

!

!

!

!

CAUTION 

!

Ground the product. 

Do not connect the ground wire to gas piping, water piping, lightning rod, 

or grounding wire of telephones.Incomplete grounding can cause electric 
shock. 

Do not install the product in the following places. 

1. An environment filled with oil or an environment where oil spray or   

steam is abundant, such as a kitchen. 

2. An environment where sulfurous acid gas or other corrosive gases are   

present. 

3. An environment where machines that generate electromagnetic waves   

are present.Electromagnetic waves may cause errors in the control   
system, hindering proper operation. 

4. An environment where flammable gases may leak or an environment   

where volatile flamma-ble substances such as thinner and gasoline are   
handled. If such gases leak and accumulate around the device,   
ignitionmay result. 

Ask your dealer or a professional to have the product installed. If you 

install the product incorrectly, electric shock or fire may result. 

Follow the instructions in this manual to securely install the product. 

Incorrect installation can cause electric shock or fire. 

Be sure to use the supplied accessories and specific components for the 

installation. If you don’t use specific components, electric shock or fire 
may result. 

Electrical installation work must be performed by an electrical installation 

service provider qualified by a power provider of the country, and be 
executed according to the technical standards and other regulations 
applicable to electrical installation in the country. Incorrect construction 
can cause electric shock or fire. 

Use appropriate wires and make secure connections. Make sure that 

external force from wires is not applied to terminals. Incomplete 
connections can cause heating or fire. 

Summary of Contents for SC-GIFN-E

Page 1: ... 3 AIR CONDITIONER CONTROL SYSTEM INTERFACE KIT SC GIFN E Manual No 12 SC T 184 ...

Page 2: ... Model 1 5 Control switch 1 6 Output switch 2 7 Wiring 2 8 Electric wiring diagram 3 9 A method of interface installation 4 10 Connectable centralized controller and gateway for connection 5 11 The number of connectable general purpose equipment 5 12 Display 6 ...

Page 3: ... Level output ON OFF factory setting Reserved SW3 1 2 SW4 1 2 1 If the network you are connecting to is the old superlink you must change this setting Whether the actual network is the new superlink or the old superlink depends on the type of indoor units outdoor units etc Check with the agent or dealer 2 For details on switching the level pulse output see6 WARNNG CAUTION Ground the product Do not...

Page 4: ... 53 Flat twin tinsel cord cord designation 60227 IEC 41 Use wires whose nominal cross sectional area is 0 75 mm2 or more for the power lines and other lines connected to the general purpose machine Make the ground wire from the wiring entrance to the interface connection area longer than the power supply lines Signal Line Specifications Communication mode Old superlink connection New superlink con...

Page 5: ... 3 8 Electric Wiring Diagram 1 To detect either operation or error only 2 To detect both operation and error Connect terminal blocks 3 and 5 ...

Page 6: ...ature range If the ambient temperature exceeds the range take measures for cooling such as installing a fan Note that using the product outside the operating temperature range can cause a malfunction Insert a circuit breaker in the power supply line Use an all pole circuit breaker whose contact gap is at least 3 mm There is risk of electric shock Make sure that the power is turned off before perfo...

Page 7: ... purpose equipment One applicable unit can only connect with per general purpose equipment Some of the general purpose equipment can operate plural unit by connecting among each of the general purpose equipments Please refer to the instruction manual of the general purpose equipment regarding the details SC SL1NA E SC SL2NA E SC SL3NA AE BE SC SL4 AE BE SC BGWN Series SC WGWN Series SC LGWN Series...

Page 8: ...al display Display when instructed Operation mode Off 1 Display as being instructed Anomalous status Normal Air flow rate No Data Display as being instructed Setting temperature deg Display as being instructed Room temperature Lower than 0deg Remote controller operation Unlock Display as being instructed Filter sign Off Display as being instructed Error code 1 Icon in Overview Monitor Screen is di...

Page 9: ... 2 AIR CONDITIONER CONTROL SYSTEM Air Conditioning Refrigeration Systems Headquarters 16 5 2 chome Kounan Minato ku Tokyo 108 8215 Japan Fax 03 6716 5926 ...

Reviews: