19
-
'19 • KX-T-336
3.4 Switching return/supply air temperature control
Normal KX indoor unit’s are control by
their EEV’s to keep system reliability.
[ Cooling ] Superheat (SH)
[ Heating ] Subcool (SC)
Return
/
supply air temperature control
Cooling mode and heating mode must use same pressure control mode.
(STANDARD mode or TYPE1 mode)
SC
= CT – liquid temp
erature
at EEV
SC
Thi-R1
Thi-R2
Thi-R3
Gas
Liquid
Heating
Flow
Flow
Thi-R1
Thi-R3
Thi-R2
SC
Thi-R1
Thi-R2
Thi-R3
Gas
Liquid
SH
Mixed
Cooling
Flow
Flow
Te
m
perature
Te
m
perature
Thi-R1
Thi-R3
Thi-R2
SH
Enthalpy
P
re
ss
ur
e
Evaporator
Condenser
Condensed
temperature (CT)
Evaporated
temperature (ET)
Compressor
EEV
SH
SC
SH
=Compressor suction temperature – ET
Control
Pressure control
mode
Target pressure / supply
air temperature setting guideline
Return air temperature
control
STANDARD
Evaporating temperature: 5-12
℃
Condensing temperature: 42-47
℃
TYPE1
Evaporating temperature: 5-12
℃
Condensing temperature: 32-37
℃
Supply air temperature
control
STANDARD
Cooling supply air temperature:
12-18
℃
Heating supply air temperature:
32-40
℃
STANDARD
(SW7-2 ON)
Cooling supply air temperature:
12-18
℃
Heating supply air temperature:
20-28
℃
TYPE1
Cooling supply air temperature:
22-28
℃
Heating supply air temperature:
20-28
℃