background image

Specification may be subject to change without notice.

DATE

TYPE

Heat Recovery Ventilator  LOSSNAY

MODEL

VL-350CZPVU-R-E

6/6

SAFETY NOTES

12-Jan-21

NUMBER

N19SGGD0003B

Duct piping

1.

When metal ducts penetrate through metal-sheeted wooden buildings or structures, install the product so that 
there is no electrical contact between the metal ducts and the metal sheeting.

2.

Secure duct piping with commercially available fixing bands, aluminum tape, etc. to prevent piping from coming 
loose. Install outdoor piping from the product so that it is tilted at a downward pitch of at least 1/30 towards the 
outside.

3.

Be sure to insulate ducts down to the base of the duct connecting flanges.

4.

Do not allow duct piping to contact the inspection opening, ceiling hanging bolts, beams, pillars, and other duct 
piping.

5.

When discharging the air from a bathroom, use ducts made of a material that does not allow water to leak.

6.

When using PCV ducts or metal ducts for the SA side ducts, be sure to connect ducts having silencer before the 
grill.

7.

Calk the duct connecting flanges that discharge air from the bathroom with calking compound. When using calking 
compound, take care to prevent it from oozing from the ducts.

Duct heater

1.

When using duct heaters (supply air preheaters, supply air after-heaters), make sure to use safety devices that do 
not have self-return functions. Do not supply the duct heaters with electricity directly from the product.

2.

When using duct heaters (supply air preheaters, supply air after-heaters) that do not have temperature control 
functions, select duct heaters that have the appropriate capacity according to the airflow passing through the 
heaters.

Drain piping

1.

Be sure to connect drain piping by the following procedure to prevent freezing and dew condensation forming on 
the surface of the piping.

- Connect the drain piping on the indoor side of the insulation layer.
- Insulate the drain piping up to the end of the piping
- Do not let the end of draing piping be immersed in the rain gutter, etc. 

(At times of heavy snow, the rain gutter freezes and drain water is not discharged, which results in water 

leaking from the Lossnay unit)

2.

Connect the drain pipe so that it has at least three degree of downward gradient from the lower part of the unit.

3.

Be sure to attach commercially available check valves.

4.

This unit has two drain pipes for EA and SA.

- Drain pipe (EA) : Piping required.
- Drain pipe (SA) : Depend on temperature and humidity, see the following conditions.

Care and attention on the use of Lossnay unit

1.

To ensure correct and safe use, read the instruction manual thoroughly.

2.

To keep the Lossnay functions in good condition for a long time, clean dirt or dust from the filters periodically.

3.

To prevent dew condensation forming on the Lossnay core and water droplets from adhering to the product 
when there is a drop in the temperature of the outside air, operation of the supply air fan is changed 
automatically.

(The exhaust fan runs continuously regardless of outdoor air temperature.)
(Even while the supply air fan has stopped, the Lossnay unit sometimes operates periodically to measure
the outdoor air temperature)

Summary of Contents for VL-350CZPVU-R-E

Page 1: ... h L s External static pressure Pa dB ErP Class Specification may be subject to change without notice DATE TYPE Heat Recovery Ventilator LOSSNAY MODEL VL 350CZPVU R E 90 150 74 38 14 1 6 35 26 19 15 SPECIFICATIONS 12 Jan 21 NUMBER N19SGGD0003B Sound Pressure level 3m A Temperature exchange efficiency Dimensions Height x Width x Depth 89 62 44 85 87 88 27 Heat recovery ventilation Bypass ventilatio...

Page 2: ...itchen 5 wet rooms Kitchen 6 wet rooms SPECIFICATIONS 30 Breakout 37 39 Air flow rate l s 21 29 37 45 53 61 0 0 20 0 40 0 60 0 80 0 100 0 120 0 60 65 70 75 80 85 90 95 0 50 100 150 200 250 300 350 0 100 200 300 400 500 Exchange efficiency Static pressure Pa Air volume 100 70 50 30 L s m3 h 55m 40m 25m φ150mm dia straight pipe length Attention Mitsubishi Electric measures figures in the chart accor...

Page 3: ... Guide EA Synthetic Resin Synthetic Resin 14 Drain pipe EA Synthetic Resin 15 Drain pipe SA Synthetic Resin 23 Air Supply Fan Synthetic Resin 18 Wall Mount Hook Top Galvanized Steel 16 PCB Under Cover Steel sheet Munsell 6 2PB 8 8 1 6 24 Air Supply Fan Motor DC 12 25 Air Exhaust Fan Synthetic Resin 04 Filter Cover SA Synthetic Resin Synthetic Resin Painted metal Munsell 6 2PB 8 8 1 6 13 10 Pipe Gu...

Page 4: ...otary switch 10 digit TAB1 TAB2 Connector Power supply SA2 Address setting rotary switch 1 digit TAB3 4 Connector Reactor SW2 SW5 to SW7 Switch TAB5 not in use CN9 CN10 Connector Fan motor SYMBOL Terminal block CN17 to CN20 Connector Connectoron PCB CN105 Connector IT Definition of symbols Attention 1 Electrical work must be carried out safely and reliably by a professional electrical contractor p...

Page 5: ...ust be higher than 15 12 Do not use duct booster fan on the RA EA duct or the OA SA duct If an external force is applied to the built in bypass damper the damper may be fixed on the bypass side when it is switching between Lossnay mode and Bypass mode and heat recovery may be prevented Installing the Lossnay unit 1 The unit is exclusively vertical mounting type 2 Do not install the product in hot ...

Page 6: ... air preheaters supply air after heaters that do not have temperature control functions select duct heaters that have the appropriate capacity according to the airflow passing through the heaters Drain piping 1 Be sure to connect drain piping by the following procedure to prevent freezing and dew condensation forming on the surface of the piping Connect the drain piping on the indoor side of the i...

Page 7: ...0 350CZPVU E Declaration of Conformity N20SGGT0062 VL 250 350CZPVU E Filter Replacement Manual 876H07701 VL 250 350CZPVU E Instruction Manual 876H46401 VL 250 350CZPVU E Parts List U295_0_DB VL 250 500CZPVU E Installation Manual 876H46502 VL 350CZPVU R E Specification Sheet N19SGGD0003B VL CZPVU R L E Homeowner Quickstart Guide Commissioning Logbook ...

Page 8: ......

Reviews: