19
l
ort
n
o
C
■
Optimal control is suitable for circuits with sharp load fluctuation. However
,
in case the load
decreases gradually when multiple capacitors are closed
,
capacitors will open from the smallest
capacity
,
and the capacitor with the largest capacity will remain last.
■
In the area where light load disconnection is not made
,
the disconnection level is determined by
the capacity. Thus this last capacitor will not be cut off.
■
When the power factor leads out further than
95
% (Changing Area) in this status
,
changing
control takes place where large capacity capacitor opens and small capacity capacitor closes.
4.8 Capacitor Changing Control at Optimal Control Operation
Setting value of Target Power Factor is not 100 %.
Changing Area
EXPORT
LEAD OUT
PROPER
LAG OUT
Light Load Disconnection Level
Disconnection Level
LEAD 95 % Level
Active Power
Connection Level
Reactive Power
LIGHT LOAD
LEAD
LAG
Setting value of Target Power Factor is 100 %.
Changing Area
EXPORT
LEAD OUT
LAG OUT
PROPER
Light Load Disconnection Level
Disconnection Level
LEAD 95 % Level
Active Power
Connection Level
Reactive Power
LIGHT LOAD
LEAD
LAG