8
Outdoor unit drainage pipe connection
When drain piping is necessary, use the drain socket or the drain pan (option).
Drain socket *
PAC-SG61DS-E
Drain pan *
KA24
PAC-SG64DP-E
KA30/36
PAC-SH97DP-E
* Do not use the drain pipe in cold climates as it may freeze.
6. Electrical work
6.1. Outdoor unit (Fig. 6-1, Fig. 6-2)
1
Remove the service panel.
2
Wire the cables referring to the Fig. 6-1 and the Fig. 6-2.
Fig. 6-1
A
C
C
E
E
E
E
E
S3
S3
S2
S1
S2
S1
L1 L2 GR
A
Indoor unit
B
Outdoor unit
C
Remote controller
D
Main switch (Breaker)
E
Earth
For Power
For Power
A
B
B
D
D
A
L1
GR
L2
S1 S2 S3
A
B
C
D
E
5. Drainage piping work
A
Earth terminal
B
Terminal block
C
Clamp
D
Service panel
E
Wire the cables so that they do
not contact the center of the
service panel or the gas valve.
CONDUIT PLATE : accessory
Fig. 6-2
Model
Max pipe length
Max height
difference
Additional refrigerant charging amount
21 m
24 m
27 m
30 m
70 ft
80 ft
90 ft
100 ft
KA24
30 m, 100 ft
30 m, 100 ft
0
0.2 kg 7 oz
0.4 kg 14 oz
0.6 kg 21 oz
KA30, 36
30 m, 100 ft
30 m, 100 ft
0
0
0
0
4.6. Addition of refrigerant
• Charge the unit with additional R410A refrigerant according to the permitted pipe
lengths in the chart below.
* When the unit is stopped, charge the unit with the additional refrigerant through
the liquid stop valve after the pipe extensions and indoor unit have been vacu-
umized.
When the unit is operating, add refrigerant to the gas check valve using a
safety charger. Do not add liquid refrigerant directly to the check valve.
* After charging the unit with refrigerant, note the added refrigerant amount on
the service label (attached to the unit).
Refer to the “1.5. Using R410A refrigerant air conditioners” for more information.
• Be careful when installing multiple units. Connecting to an incorrect indoor unit
can lead to abnormally high pressure and have a serious effect on operation per-
formance.
4. Installing the refrigerant piping
en
BH79D886H08_01en.indd 8
2021/12/23 11:06:35