'15 • SRK-T-171
(9) Protective control function
(a) Frost prevention for indoor heat exchanger
(During cooling or dehumidifying)
(i) Operating conditions
1)
Indoor heat exchanger temperature (Th2) is lower than 2.5ºC.
2)
3 minutes elapsed after the start of operation.
(ii) Detail of frost prevention operation
Compressor
OFF
Indoor fan
Protects the fan tap just before frost prevention control.
Outdoor fan
Depending on the stop mode
(iii) Reset condition:
Indoor heat exchanger temperature (Th2) is higher than 15ºC.
(b) Indoor fan motor protection
When the airconditioner is operating and the indoor fan motor is turned ON, if the indoor fan motor has operated at 300 min
-1
or
under for more than 30 seconds, the unit enters first in the stop mode and then stops the entire system.
TIMER light illuminates simultaneously and the RUN light flashing 6-time at each 8-second.
(c) 3 minutes forced operation
When the compressor begins operating the thermal operation is not effective for 3 minutes, so operation continues as is in the
operation mode. (After 3 minutes has passed the thermal operation is effective.)
However, stopping the compressor via a stop signal or protection control has priority.
(d) Abnormality of outdoor unit
After the compressor run 5 minutes, and the indoor heat exchanger temperature more than 25ºC continuously more than 40 minutes,
then the abnormality stop occurs.
(e) Sensor disconnection (room temperature, indoor heat exchanger)
(i) Room temperature sensor
If the temperature detected by the room temperature sensor is – 45ºC or lower, continuously for 15 seconds or longer, then
operation is stopped, an error indication is displayed. (RUN light: 2-time flash, TIMER light: ON)
(ii) Indoor heat exchanger temperature sensor
If the temperature detected by the indoor heat exchanger temperature sensor is –28ºC or lower, continuously for 15 seconds
or longer, then operation is stopped, an error indication is displayed.
(RUN light : 1-time flash, TIMER light : ON)
Summary of Contents for SRK05CR-S
Page 2: ......
Page 3: ... 15 SRK T 171 TECHNICAL MANUAL ...
Page 32: ... 30 15 SRK T 171 3 Wireless remote control Unit mm 60 17 3 150 All models Unit mm 60 17 3 150 ...
Page 70: ... 68 15 SRK T 171 ...
Page 72: ... 70 15 SRK T 171 ...
Page 74: ... 72 15 SRK T 171 ...
Page 76: ... 74 15 SRK T 171 ...
Page 78: ... 76 15 SRK T 171 ...
Page 80: ... 78 15 SRK T 171 ...
Page 82: ... 80 15 SRK T 171 ...
Page 84: ... 82 15 SRK T 171 ...
Page 86: ... 84 15 SRK T 171 ...
Page 88: ... 86 15 SRK T 171 ...
Page 90: ... 88 15 SRK T 171 ...
Page 92: ... 90 15 SRK T 171 ...
Page 94: ... 92 15 SRK T 171 ...
Page 96: ... 94 15 SRK T 171 ...
Page 98: ... 96 15 SRK T 171 ...
Page 100: ... 98 15 SRK T 171 ...
Page 102: ... 100 15 SRK T 171 ...
Page 104: ... 102 15 SRK T 171 ...
Page 106: ... 104 15 SRK T 171 ...
Page 108: ... 106 15 SRK T 171 ...
Page 110: ... 108 15 SRK T 171 ...
Page 112: ... 110 15 SRK T 171 ...
Page 114: ... 112 15 SRK T 171 ...
Page 116: ... 114 15 SRK T 171 ...