Unit : mm
SEZ-KD25VA(L)
SEZ-KD35VA(L)
SEZ-KD50VA(L)
SEZ-KD60VA(L)
SEZ-KD71VA(L)
SEZ-KD60, 71
SEZ-KD35, 50
700
50~150
800
1300
1000
P
Model
SEZ-KD25
150~250
Q
900
R
1500
1200
250~350
1100
1700
S
(mm)
Electric box
Ceiling
Min. 300 mm
Min. 10 mm
A
Access door 2 (450 x 450)
Ceiling beam
Intake air
Supply air
Electric box
Ceiling
Min. 20 mm
Min.10 mm
B
Ceiling beam
Access door 3
Intake air
Supply air
700
450
475
450
Q
50~150
450
450
100~200
Bottom of indoor unit
Maintenance access space
Min. 300 mm
(Viewed from the direction of
the arrow A)
Access door 2
(450 x 450)
Access door 1
(450 x 450)
P
Electric box
Access door 3
P
50
R
777
450
100~200
Maintenance access space
Bottom of indoor unit
Electric box
(Viewed from the direction of
the arrow B)
Access door 1
(450 x 450)
450
475
700
50
Min. 300 mm
Fig. 1
Fig. 3
Fig. 2
Fig. 4
Secure enough access space to allow for the maintenance, inspection, and replacement of the motor, fan, drain pump, heat
exchanger, and electric box in one of the following ways.
Select an installation site for the indoor unit so that its maintenance access space will not be obstructed by beams or other
objects.
(1) When a space of 300 mm or more is available below the unit between the unit and the ceiling (Fig. 1)
• Create access door 1 and 2 (450 x 450 mm each) as shown in Fig. 2.
(Access door 2 is not required if enough space is available below the unit for a maintenance worker to work in).
(2) When a space of less than 300 mm is available below the unit between the unit and the ceiling (At least 20 mm of space
should be left below the unit as shown in Fig. 3.)
• Create access door 1 diagonally below the electric box and access door 3 below the unit as shown in Fig. 4.
or
• Create access door 4 below the electric box and the unit as shown in Fig. 5.
777
S
50
50
P
700
Maintenance access space
Bottom of indoor unit
Electric box
Min. 300 mm
(Viewed from the direction of
the arrow B)
Access door 4
Fig. 5