Check of LEV
No
Yes
Yes
No
Turn ON the breaker to the outdoor unit after checking LEV
coil is mounted to the LEV body securely.
Is "click - click" sound heard?
Or, do you feel vibration of LEV coil with your hand?
Disconnect the connectors.
MXZ-2D
CN724: LEV A, CN725: LEV B
Other models
CN791: LEV A, CN792: LEV B,
CN793: LEV C, CN794: LEV D,
CN795: LEV E, CN796: LEV F
Normal
Is the resistance of the LEV coil normal?
(Refer to 11-5.)
Replace the inverter P.C. board or
the outdoor control P.C. board.
Replace LEV coil.
• In cooling, the heat exchanger of non-operating indoor unit has frosted.
• In heating, non-operating indoor unit gets warm.
CN724
CN725
CN793
CN794
CN795
CN796
Outdoor
control
P.C. board
MXZ-3D/4D/5D
MXZ-2D
Inverter
P.C. board
OBH626E
Summary of Contents for SEZ-KD VA Series
Page 22: ...22 MXZ 2D33VA E2 MXZ 2D42VA E2 MXZ 2D53VA E2 OBH626E ...
Page 23: ...23 MXZ 2D33VA ER2 MXZ 2D40VA ER2 MXZ 2D53VA ER2 OBH626E ...
Page 24: ...24 MXZ 2D53VAH E1 OUTDOOR DISPLAY P C BOARD OBH626E ...
Page 25: ...25 MXZ 2D53VAH E2 OBH626E ...
Page 26: ...26 MXZ 2D53VAH ER2 OBH626E ...
Page 27: ...27 MXZ 3D54VA E1 OBH626E ...
Page 28: ...28 MXZ 3D54VA2 E2 OBH626E ...
Page 29: ...29 MXZ 3D54VA2 ER2 OBH626E ...
Page 30: ...30 MXZ 3D68VA E1 OBH626E ...
Page 31: ...31 MXZ 3D68VA E2 OBH626E ...
Page 32: ...32 MXZ 3D68VA ER2 OBH626E ...
Page 33: ...33 MXZ 4D72VA E1 OBH626E ...
Page 34: ...34 MXZ 4D72VA E2 OBH626E ...
Page 35: ...35 MXZ 4D72VA ER2 OBH626E ...
Page 36: ...36 MXZ 4D83VA E1 OBH626E ...
Page 37: ...37 MXZ 4D83VA E2 OBH626E ...
Page 38: ...38 MXZ 4D83VA ER1 OBH626E ...
Page 39: ...39 MXZ 4D83VA ER2 OBH626E ...
Page 40: ...40 MXZ 5D102VA E1 OBH626E ...
Page 41: ...41 MXZ 5D102VA E2 OBH626E ...
Page 42: ...42 MXZ 5D102VA ER1 OBH626E ...
Page 43: ...43 MXZ 5D102VA ER2 OBH626E ...