1 FUNCTIONS
1.5 IP Packet Transfer Function
53
1
Example of communications using the IP packet transfer function
When the request source and destination devices have the same network address
The following system configuration is used to explain an example of communications.
■
Setting in the CPU module 1 and master station (station No.0)
1.
Set the IP address of the CPU module 1 as follows.
Navigation window
"Parameter"
Target module
"Module Parameter"
"Basic Settings"
"Own Node Settings"
"IP Address"
2.
Change the following setting to "Use" in the CPU module 1.
Navigation window
"Parameter"
Target module
"Module Parameter"
"Application Settings"
"IP Packet
Transfer Setting"
3.
Set the IP address of the master station (station No.0) as follows.
Navigation window
"Parameter"
"Module Information"
Target module
"Module Parameter (Network)"
"Application Settings"
"IP Address"
4.
Write the set parameters to the CPU module 1. Then reset the CPU module 1 or power off and on the system.
Ethernet device
(request source device)
192.168.1.1
: Route through which IP packets are passed
Network No.1
Network No.10
CPU module 1: 192.168.1.10
Master station: 192.168.2.125
(station No.0)
CPU module 2: 192.168.10.10
Local station: 192.168.2.2
(station No.2)
Network No.2
Ethernet device
(request destination device)
192.168.10.1