3.4.2
D/A conversion enable/disable setting (Un\G0)
(1) Set whether D/A conversion is enabled or disabled for each channel.
(2) To validate the settings, on/off of Operating condition setting request (Y9) is required.
(Refer to Section 3.3.2.)
(3) By default, all channels are set to D/A conversion disabled.
Design the system so that D/A conversion enable/disable setting (Un\G0)
changes to "Enable" after the external power (Refer to Section 4.3) is supplied.
Analog output may not be performed properly if the external power is not at the
specified voltage.
3.4.3
CH
[ ]
Digital value (Un\G1 to Un\G6)
(1) This area is used to write digital values from the programmable controller CPU as 16-
bit signed binary code.
(2) If a value outside the settable range is written, the upper or lower limit value of the
range is used for D/A conversion. (Refer to Table3.7.)
Also, if this happens, a check code and an error code will be stored in the CH Set
value check code (Un\G11 to Un\G16) and Error code (Un\G19) respectively.
Table3.7 Output range settings and settable range
Output range setting
Normal resolution mode
High resolution mode
Settable range
(practical range)
Digital value that is set when
a value outside the settable
range is written
Settable range
(practical range)
Digital value that is set when
a value outside the settable
range is written
0: 4 to 20 mA
-96 to 4095
(Practical range:
0 to 4000)
4096 or larger: 4095
-97 or smaller: -96
-288 to 12287
(Practical range:
0 to 12000)
12288 or larger: 12287
-289 or smaller: -288
1: 0 to 20 mA
2: 1 to 5 V
3: 0 to 5 V
4: –10 to 10 V
-4096 to 4095
(Practical range:
-4000 to 4000)
4096 or larger: 4095
-4097 or smaller: -4096
-16384 to 16383
(Practical range:
-16000 to 16000)
16384 or larger: 16383
-16385 or smaller: -16384
A: 4 to 20mA
(Extended mode)
-1096 to 4595
(Practical range:
- 1000 to 4500)
4596 or larger: 4595
-1097 or smaller: -1096
-3288 to 13787
(Practical range:
-3000 to 13500)
13788 or larger: 13787
-3289 or smaller: -3288
B: 1 to 5V
(Extended mode)
D: User range setting3
-4096 to 4095
(Practical range:
-4000 to 4000)
4096 or larger: 4095
-4097 or smaller: -4096
-12288 to 12287
(Practical range:
-12000 to 12000)
12288 or larger: 12287
-12289 or smaller: -12288
E: User range setting2
F: User range setting1
b15
b14
b13
b12
b11
b10
b9
b8
b7
b6
b5
b4
b3
b2
b1
b0
CH
2
CH
1
CH
4
CH
3
CH
6
CH
5
1: D/A conversion disabled
0: D/A conversion enabled
Un\G0
0
0
0
0
0
0
0
b6 to b15 information is fixed at 0.
0
0
0