7.3 Online Module Change Procedure
7.3.6 When user range setting is used and initial setting was made with sequence program (other system is
7
ONLINE MODULE CHANGE
(c) After confirming that the "RUN" LED of the module has turned off, remove the
connector and dismount the module.
Always perform the dismounting procedure. If mounting confirmation is made
without the module being dismounted, the module will not start properly and the
"RUN" LED will not be lit.
(3) Mounting of new module
(a) Mount a new module to the same slot and install the connector.
(b) After mounting the module, click the [Execution] button and make sure that the
"RUN" LED is lit. Module READY (X0) remains off.
(4) Operation check
(a) To make an operation check, click the [Cancel] button to cancel control
resumption.