background image

1

This CO

2

 sensor optimizes the amount of airflow in accordance with the CO

2

 concentration within the room, and thus reduces the fresh air load.

■  This manual must be read both fully and carefully before commencing installation procedures; furthermore, the subsequent installation must be 

performed correctly and safely in accordance with the instructions given.

■  After installation, ensure that this manual is given to the customer.

1. Safety Precautions

 

WARNING

Incorrect handling could cause serious injury or death.

-  Never modify or repair by yourself.

If the product is modified or inappropriately repaired, electric shock, fire, etc. could result. Contact your dealer for repair.

-  Do not move or reinstall the product by yourself. 

If it is installed improperly, electric shock, fire, etc. could result. Contact your dealer or technical representative. 

- Use the specified cables for wiring and connect them securely. Hold the cables so as not to apply external force of the cables to the 

connector. 

Improper connection could result in heat generation or fire.

- All electrical work must be performed by a licensed technician, according to local regulations and the instructions given in this Installation 

manual.

Ensure that installation work is done correctly following this Installation manual.

If it is installed improperly, electric shock, fire, etc. could result.

-  Close the control cover after installation.

- Do not install the product in a place where flammable gases may leak.

If gas should leak or accumulate around the product, fire or explosion could result. 

-  Do not use the product in special environments. 

The product could be damaged if it is used in locations subject to large quantities of oil (including machine oil), steam, or sulfide gas. 

- Do not install the unit in a place where the temperature rises above 40 ˚C (104°F), where large amounts of oil, steam, organic solvents, or 

corrosive gases, such as sulfuric gas, are present, or where acidic/alkaline solutions or sprays are used frequently. 

These substances can compromise the performance of the unit or cause certain components of the unit to corrode, which can result in electric shock, 

malfunctions, smoke, or fire.

 CAUTION

Incorrect handling could cause injury or damage to property or household effects.

-  Wire so that it does not receive any tension.

Tension could cause wire breakage, heating or fire.

- Put on gloves during installation.

Failure to do so could cause injury. 

Lossnay CO

2

 Sensor Built-In Type

PZ-70CSB-E

Installation and Instruction Manual

2107876H65301

Summary of Contents for PZ-70CSB-E

Page 1: ...structions given in this Installation manual Ensure that installation work is done correctly following this Installation manual If it is installed improperly electric shock fire etc could result Close the control cover after installation Do not install the product in a place where flammable gases may leak If gas should leak or accumulate around the product fire or explosion could result Do not use...

Page 2: ...ontrol box cover 2 Remove the Lossnay cores 3 Check that the installation screw hole positioning plate is affixed in the ventilation path RA 3 2 CO2 sensor installation 1 Temporarily tighten the installation screw included at the position indicated by on the installation positioning plate After hooking CO2 sensor key hole on the temporary screw align on the plate with the screw holes and fully tig...

Page 3: ...al technician is to carry out connection work Once installation work is complete confirm again that wiring is as per the wiring diagram and that no parts or screws remain unused Do not disconnect connectors that are already connected 4 1 CO2 sensor connector connection Pull the CO2 sensor cable into the Lossnay unit circuit box In order to protect the edge pass through the packing included with th...

Page 4: ...nizes the lowest CO2 concentrations such as at night or when there are fewer people coming and going as the standard value corresponding to normal outside CO2 concentrations and corrects these correspondingly therefore the CO2 concentrations detected by the CO2 sensor and the actual CO2 concentration within the room may differ Therefore if this product is used in locations in which the outside CO2...

Page 5: ...d however given that CO2 concentration detection will differ depending on the usage environment and product installation conditions the value may exceed upper limit depending on the usage environment If not using a remote controller automatic airflow control will be carried out at the factory default setting Factory default setting Upper limit 1000 ppm lower limit 450 ppm Example Auto fan speed wi...

Page 6: ...m at the start of operation with the Auto fan speed sensing operation is performed at fan speed 4 for about 15 minutes After sensing is completed the fan speed is automatically switched according to the CO2 concentration The remote controller displays the fan speed on a scale of 1 to 4 For the 16 steps fan speed by the automatic fan speed control During 25 to 45 fan speed operation it displays the...