11-3-5. Pump Interlock
11. SYSTEM DESIGN
The unit may become damaged if it is operated with no water circulating through the pipes.
Be sure to interlock unit operation and the water-circuit pump. Use the terminal blocks for interlocking TB142A (IN1)
that can be found on the unit.
IN1
TB142A
Water Pump
Strainer
Control Box
Broken lines are field
supply products.
Operation signal
Pump interlock
Pump Interlock Example Diagram