98
OPERATING PROCEDURE
PHOTOS
11. Removing the reactor (DCL) and capacitor (CB)
(1) Remove the service panel. (See Figure 1)
(2) Remove the top panel. (See Figure 1)
(3) Remove the electrical parts box. (See Photo 3)
[Removing the reactor]
(4) Remove the reactor fixing screws (4 for rear/4 × 10) and
remove the reactor.
[Removing the capacitor]
(4) Remove the capacitor band fixing screws (2 for rear/
4 × 10) and remove the capacitor.
(The reactor and capacitor are fixed to the electrical parts
box on the rear side.)
12. Removing the compressor (MC)
(1) Remove the service panel. (See Figure 1)
(2) Remove the top panel. (See Figure 1)
(3) Remove the electrical parts box. (See Photo 3)
(4) Remove the cover panel (front). (See Figure1)
(5) Remove the cover panel (rear). (See Photo 3)
(6) Remove the valve bed. (See Photo 10)
(7) Remove the side panel (R). (See Photo 3)
(8) Remove the front panel fixing screws (4 for front/ 5x12
and 2 for front/ 4x10), then slide the front panel upward
to remove it. (The front panel is fixed with 4 hooks; 3 on
the left side fixing to the side panel (L), and the other on
the right side fixing to the separator.)
(9) Remove the separator fixing screws (3 for front/ 4x10),
then slide the separator upward to remove it. (The
separator is fixed to a hook of the side plate.)
(10) Recover refrigerant.
(11) Remove the welded part of compressor (2 positions).
(12) Remove the 3 compressor fixing nuts (M6) to remove the
compressor.
Note 1: Recover refrigerant without spreading it in the air.
Note 2: The compressor can be easily removed by
removing separator.
Capacitor band
fixing screws
Photo 9
Reactor
fixing
screws
Reactor
fixing
screws
Reactor
(DCL)
Electrical parts box
Capacitor (CB)
Photo 10
Compressor (MC)
Valve bed
Separator
Power receiver
Compressor fixing nuts
OCH607
Summary of Contents for PUZ-HA30NHA5