3. Combination of outdoor units
Component units of PURY-P168 to P288 are listed below.
Outdoor unit model
Component unit model
PURY-P72TJMU-A(-BS)
-
-
PURY-P96TJMU-A(-BS)
-
-
PURY-P120TJMU-A(-BS)
-
-
PURY-P144TJMU-A(-BS)
-
-
PURY-P168TSJMU-A(-BS)
PURY-P96TJMU-A(-BS)
PURY-P72TJMU-A(-BS)
PURY-P192TSJMU-A(-BS)
PURY-P96TJMU-A(-BS)
PURY-P96TJMU-A(-BS)
PURY-P216TSJMU-A(-BS)
PURY-P120TJMU-A(-BS)
PURY-P96TJMU-A(-BS)
PURY-P240TSJMU-A(-BS)
PURY-P120TJMU-A(-BS)
PURY-P120TJMU-A(-BS)
PURY-P264TSJMU-A(-BS)
PURY-P144TJMU-A(-BS)
PURY-P120TJMU-A(-BS)
PURY-P288TSJMU-A(-BS)
PURY-P144TJMU-A(-BS)
PURY-P144TJMU-A(-BS)
Component units of PURY-P168 to P288 are listed below.
Outdoor unit model
Component unit model
PURY-P72YJMU-A(-BS)
-
-
PURY-P96YJMU-A(-BS)
-
-
PURY-P120YJMU-A(-BS)
-
-
PURY-P144YJMU-A(-BS)
-
-
PURY-P168YSJMU-A(-BS)
PURY-P96YJMU-A(-BS)
PURY-P72YJMU-A(-BS)
PURY-P192YSJMU-A(-BS)
PURY-P96YJMU-A(-BS)
PURY-P96YJMU-A(-BS)
PURY-P216YSJMU-A(-BS)
PURY-P120YJMU-A(-BS)
PURY-P96YJMU-A(-BS)
PURY-P240YSJMU-A(-BS)
PURY-P120YJMU-A(-BS)
PURY-P120YJMU-A(-BS)
PURY-P264YSJMU-A(-BS)
PURY-P144YJMU-A(-BS)
PURY-P120YJMU-A(-BS)
PURY-P288YSJMU-A(-BS)
PURY-P144YJMU-A(-BS)
PURY-P144YJMU-A(-BS)
4. Specifi cations
Model
PURY-
P72TJMU-A(-BS)
PURY-
P96TJMU-A(-BS)
PURY-
P120TJMU-A(-BS)
PURY-
P144TJMU-A(-BS)
PURY-
P168TSJMU-A(-BS)
PURY-
P192TSJMU-A(-BS)
PURY-
P216TSJMU-A(-BS)
PURY-
P240TSJMU-A(-BS)
PURY-
P264TSJMU-A(-BS)
PURY-
P288TSJMU-A(-BS)
Sound level (60Hz)
58dB<A>
58dB<A>
60dB<A>
61dB<A>
61dB<A>
61dB<A>
62.5dB<A>
63dB<A>
63.5dB<A>
64dB<A>
External static pressure
0 Pa *2
Indoor
units
Total capacity
50 ~ 150% *1
Model
06 ~ 96
Quantity
1 ~ 18
1 ~ 24
1 ~ 30
1 ~ 36
1 ~ 42
1 ~ 48
2 ~ 50*
2 ~ 50*
2 ~ 50*
2 ~ 50*
Operation
temperature
Standard type
Cooling mode:
í
5°CDB ~ 46°CDB [23°FDB ~ 115°FDB]
Heating mode:
í
20°CWB ~ 15.5°CWB [
í
4°FWB ~ 60°FWB]
Outside air
intake type
Cooling mode: 21°CDB/15.5°CWB ~ 46°CDB/35°CWB [70°FDB/60°FWB ~ 115°FDB/95°FWB]
Heating mode:
í
12.5°CWB ~ 20°CWB [
í
9.5°FWB ~ 68°FWB]
Model
PURY-
P72YJMU-A(-BS)
PURY-
P96YJMU-A(-BS)
PURY-
P120YJMU-A(-BS)
PURY-
P144YJMU-A(-BS)
PURY-
P168YSJMU-A(-BS)
PURY-
P192YSJMU-A(-BS)
PURY-
P216YSJMU-A(-BS)
PURY-
P240YSJMU-A(-BS)
PURY-
P264YSJMU-A(-BS)
PURY-
P288YSJMU-A(-BS)
Sound level (60Hz)
58dB<A>
58dB<A>
60dB<A>
61dB<A>
61dB<A>
61dB<A>
62.5dB<A>
63dB<A>
63.5dB<A>
64dB<A>
External static pressure
0 Pa *2
Indoor
units
Total capacity
50 ~ 150% *1
Model
06 ~ 96
Quantity
1 ~ 18
1 ~ 24
1 ~ 30
1 ~ 36
1 ~ 42
1 ~ 48
2 ~ 50*
2 ~ 50*
2 ~ 50*
2 ~ 50*
Operation
temperature
Standard type
Cooling mode:
í
5°CDB ~ 46°CDB [23°FDB ~ 115°FDB]
Heating mode:
í
20°CWB ~ 15.5°CWB [
í
4°FWB ~ 60°FWB]
Outside air
intake type
Cooling mode: 21°CDB/15.5°CWB ~ 46°CDB/35°CWB [70°FDB/60°FWB ~ 115°FDB/95°FWB]
Heating mode:
í
12.5°CWB ~ 20°CWB [
í
9.5°FWB ~ 68°FWB]
*Connectable branch pipe number is max. 48.
*1: The total indoor capacity of units run simultaneously is 150% or less.
*2: To enable high static pressure, set the DipSW on the main panel as follows.
SW3-9: ON, SW3-10 60Pa compatible: OFF, 30Pa compatible: ON