85
OPERATING PROCEDURE
PHOTOS
13. High pressure sensor (63HS)disassembly procedures:
(1) Remove the side panel (See photo 1).
(2) Remove the high pressure sensor wire.
(3) Recover gas from the refrigerant circuit.
(4) Remove the welded portion of high pressure sensor.
(5) Remove the mounting screw fastening the high
pressure sensor mounting plate (1 pc : 4
o
10).
(6) Remove the high pressure sensor mounting screws
(2 pcs : 4
o
10).
Photo 14
Photo 15
14. Capillary tube disassembly procedures:
(1) Remove the side panel (See photo 1).
(2) Remove the top panel (See photo 1).
(3) Remove the electrical parts box (See photo 5 or 6).
(4) Recover gas from the refrigerant circuit.
(5) Remove the field piping from the unit (liquid side)
(6) Remove the welded portions of capillary tube.
✻
To remove welded portions, cut the band holding it and
remove the rubber tube.
High pressure
sensor mount
Separator
High pressure
sensor
Welding part
fixing screw
Capillary tube 1
Capillary tube 2
Capillary tube 3
Capillary tube 4