10

2

Wiring examples

• Controller name, symbol and allowable number of controllers.

2. M-NET Remote control cables

Kind of remote control cable

Cable diameter

Remarks

Shielding wire MVVS
0.5 to 1.25 mm

2

When 10 m is exceeded, use cable with the
same specifications as transmission line wiring

Name

Outdoor unit controller
Indoor unit controller

Remote controller

Symbol

OC

IC

RC

(M-NET)

MA

Allowable number of controllers

One to eight controllers for one OC
Maximum of 16 controllers for one
OC
Maximum of two per group

6.3. Wiring transmission cables

1

Types of control cables

1. Wiring transmission cables
• Types of transmission cables: Shielding wire CVVS or CPEVS
• Cable diameter: More than 1.25 mm

2

• Maximum wiring length: Within 200 m

Example of a group operation system with multiple outdoor units (Shielding wires and address setting are

necessary.)

<Examples of Transmission Cable Wiring>

M-NET Remote Controller (Fig. 6-2)

MA Remote Controller (Fig. 6-3)

<Wiring Method and Address Settings>
a. Always use shielded wire when making connections between the outdoor unit (OC) and the indoor unit (IC), as well for all OC-OC, and IC-IC wiring intervals.
b. Use feed wiring to connect terminals M1 and M2 and the ground terminal on the transmission cable terminal block (TB3) of each outdoor unit (OC) to terminals M1, M2

and terminal S on the transmission cable block of the indoor unit (IC).

c.

Connect terminals 1 (M1) and 2 (M2) on the transmission cable terminal block of the indoor unit (IC) that has the most recent address within the same group to the
terminal block on the remote controller (RC).

d. Connect together terminals M1, M2 and terminal S on the terminal block for central control (TB7) for the outdoor unit (OC).
e. The jumper connector CN41 on the control panel does not change.
f.

Connect shield ground of the indoor units transmission line to the shield (S) terminal of (TB3) and also connect (S) terminal to screw 

C

 or 

D

 using attached lead wire.

Connect shield ground of the line between outdoor units and the central control system transmission line to the shield (S) terminal of (TB7).

g. Set the address setting switch as follows.

Unit

Range

Setting Method

IC (Main)

01 to 50

Use the most recent address within the same group of  indoor units

IC (Sub)

01 to 50

Use an address, other than that of the IC (Main) from among the units within the same group of indoor units. This must be
in sequence with the IC (Main)

Outdoor Unit

51 to 100

Use the most recent address of all the indoor units plus 50
* The address automatically becomes “100” if it is set as “01 - 50”.

M-NET R/C (Main)

101 to 150

Set at an IC (Main) address within the same group plus 100

M-NET R/C (Sub)

151 to 200

Set at an IC (Main) address within the same group plus 150

MA R/C

Unnecessary address setting (Necessary main/sub setting)

h. The group setting operations among the multiple indoor units is done by the remote controller (RC) after the electrical power has been turned on.

<Permissible Lengths>

1

M-NET Remote controller

Max length via outdoor units: L

1

+L

2

+L

3

+L

4

 and L

1

+L

2

+L

3

+L

5

 and L

1

+L

2

+L

6

+L

7

 

=

 500 m (1.25 mm

2

 or more)

Max transmission cable length: L

and L

3

+L

4

 and L

3

+L

5

 and L

6

 and L

2

+L

6

 and L

7

 

=

 200 m (1.25 mm

2

 or more)

Remote controller cable length:

r

1

r

2

r

2

+

r

3

r

4

  

=

 10 m (0.5 to 1.25 mm

2

)

If the length exceeds 10 m, use a 1.25 mm

2

 shielded wire.  The length of this section (L

8

) should be included in the calculation of the

maximum length and overall length.

2

MA Remote controller

Max length via outdoor unit (M-NET cable): L

1

+L

2

+L

3

+L

4

 and L

1

+L

2

+L

6

+L

7

 

=

 500 m (1.25 mm

2

 or more)

Max transmission cable length (M-NET cable): L

and L

3

+L

4

 and L

6

 and L

2

+L

6

 and L

7

 

=

 200 m (1.25 mm

or more)

Remote controller cable length:

c

1

 and 

c

1

+

c

2

 +

c

3

 and 

c

1

+

c

2

+

c

3

+

c

4  

=

 200 m (0.3 to 1.25 mm

2

)

6. Electrical work

M1

S

M2

B

C

M1

S

M2

TB3

TB7

D

A

L1 L2 L3 N

3. MA Remote control cables

Kind of remote control cable

Cable diameter

2-core cable (unshielded)
0.3 to 1.25 mm

2

A

 : Power source

B

 : Transmission line

C

 : Screw on the electrical component box

D

 : Screw on the electrical component box

6.2. Control box and connecting position of wiring

(Fig. 6-1)

1. Connect the indoor unit transmission line to transmission terminal block (TB3), or

connect the wiring between outdoor units or the wiring with the centralized con-
trol system to the centralized control terminal block (TB7).
When using shielded wiring, connect shield ground of the indoor unit transmis-
sion line to the screw (

C

 or 

D

) and connect shield ground of the line between

outdoor units and the central control system transmission line to the shield (S)
terminal of the centralized control terminal block (TB7) shield (S) terminal. In
addition, in the case of outdoor units whose power supply connector CN41 has
been replaced by CN40, the shield terminal (S) of terminal block (TB7) of the
centralized control system should also be connected to the screw 

C

 or 

using

attached lead wire.

2. Conduit mounting plates (ø27) are being provided. Pass the power supply and

transmission wires through the appropriate knock-out holes, then remove the
knock-out piece from the bottom of the terminal box and connect the wires.

3. Fix power source wiring to terminal box by using buffer bushing for tensile force

(PG connection or the like).

Fig. 6-1

Summary of Contents for PUMY-P-YHMA

Page 1: ...ll unità interna prima di installare il condizionatore d aria MANUAL DE INSTALACIÓN Para un uso correcto y seguro lea detalladamente este manual y el manual de instalación de la unidad interior antes de instalar la unidad de aire acondicionado E XEIPI IO O H IøN E KATA TA H È ÛˆÛÙ Î È ÛÊ Ï Ú ÛË È ÛÙÂ ÚÔÛÂÎÙÈÎ Ùfi ÙÔ ÂÁ ÂÈÚ ÈÔ Î ıÒ Î È ÙÔ ÂÁ ÂÈÚ ÈÔ ÂÁÎ Ù ÛÙ ÛË ÙË ÂÛˆÙÂÚÈÎ ÌÔÓ ÚÔÙÔ ÂÁÎ Ù ÛÙ ÛÂÙÂ ÙË Ì...

Page 2: ...n cause pressure peaks resulting in a rupture and other hazards Use only accessories authorized by Mitsubishi Electric and ask a dealer or an authorized technician to install them If accessories are incorrectly in stalled water leakage electric shock or fire may result Do not alter the unit Consult a dealer for repairs If alterations or repairs are not performed correctly water leakage electric sh...

Page 3: ... refrigeration oil oil deterioration may result Do not use refrigerant other than R410A refrigerant If another refrigerant is used the chlorine will cause the oil to deteriorate Use the following tools specifically designed for use with R410A refrigerant The following tools are necessary to use R410A refrigerant Contact your nearest dealer for any questions Tools for R410A Gauge manifold Flare too...

Page 4: ...tdoor unit to transport the unit If the unit is carried from the bottom hands or fingers may be pinched 2 3 Outline dimensions Outdoor unit Fig 2 1 Constraints on indoor unit installation You should note that indoor units that can be connected to this outdoor unit are the following models Indoor units with model numbers 15 140 PUMY P100 15 125 can be connected Refer to the table below for possible...

Page 5: ...t rear sides and above only Fig 2 7 Do not install the optional air outlet guides for upward airflow 2 4 2 When installing multiple outdoor units Leave 10 mm space or more between the units 1 Obstacles at rear only Fig 2 8 2 Obstacles at rear and above only Fig 2 9 No more than three units must be installed side by side In addition leave space as shown Do not install the optional air outlet guides...

Page 6: ... less and install on site Warning The unit must be securely installed on a structure that can sustain its weight If the unit is mounted on an unstable structure it may fall down and cause damage or injuries The unit must be installed according to the instructions in order to minimize the risk of damage from earthquakes typhoons or strong winds An incor rectly installed unit may fall down and cause...

Page 7: ...usual pipe sealing is used refer to Table 1 for flaring of R410A refrigerant pipes The size adjustment gauge can be used to confirm A measurements A mm Å Liquid pipe ı Gas pipe PUMY P100 140 ø9 52 ø15 88 B C D mm Ç Total capacity of indoor units Å Liquid pipe ı Gas pipe ø9 52 ø15 88 a b c d e f mm Î Model number Å Liquid pipe ı Gas pipe 15 20 25 32 40 50 ø6 35 ø12 7 63 80 100 125 140 ø9 52 ø15 88 ...

Page 8: ...sure does not decrease 2 Pressurize to 1 5 MPa 15 kgf cm2 G wait five minutes and make sure the pressure does not decrease 3 Pressurize to 4 15 MPa 41 5 kgf cm2 G and measure the surrounding tem perature and refrigerant pressure 3 If the specified pressure holds for about one day and does not decrease the pipes have passed the test and there are no leaks If the surrounding temperature changes by 1...

Page 9: ...ork to outdoor unit 4 Give some allowance to wiring for electrical part box of indoor and outdoor units because the box is sometimes removed at the time of service work 5 Never connect the main power source to terminal block of transmission line If connected electrical parts will be burnt out 6 Use 2 core shield cable for transmission line If transmission lines of different systems are wired with ...

Page 10: ...utomatically becomes 100 if it is set as 01 50 M NET R C Main 101 to 150 Set at an IC Main address within the same group plus 100 M NET R C Sub 151 to 200 Set at an IC Main address within the same group plus 150 MA R C Unnecessary address setting Necessary main sub setting h The group setting operations among the multiple indoor units is done by the remote controller RC after the electrical power ...

Page 11: ...is one compatible with higher harmonics Always use a current leakage breaker that is compatible with higher harmonics as this unit is equipped with an inverter The use of an inadequate breaker can cause the incorrect operation of inverter 16 A 30 mA 0 1 sec or less 15 A 30 mA 0 1 sec or less 16 A 15 A 1 5 1 5 1 5 1 5 Indoor Unit Main Cable Minimum Wire Thickness mm2 Branch Breaker for Current Leak...

Page 12: ...nifold valve and put the cap back onto each stop valve Note 1 Never carry out pump down operation if the amount of refrigerant inside the indoor unit is larger than the amount of charge less refrigerant Carrying out a pump down operation when the amount of refrigerant ex ceeds the amount of charge less refrigerant will cause an extreme pres sure rise and may result in an accident 2 Do not continue...

Page 13: ...2006 95 EC Electromagnetic Compatibility Directive 89 336 EEC This product is designed and intended for use in the residential commercial and light industrial environment HEAD OFFICE TOKYO BLDG 2 7 3 MARUNOUCHI CHIYODA KU TOKYO 100 8310 JAPAN Printed in Japan BG79U713H04 The product at hand is based on the following EU regulations ...

Reviews: