Outdoor power circuit board
Brief Check of POWER MODULE
Usually, they are in a state of being short-circuited if they are broken.
Measure the resistance in the following points (connectors, etc.).
If they are short-circuited, it means that they are broken.
1. Check of POWER MODULE
1
Check of DIODE circuit
R - P1 , S - P1 , R - N1 , S - N1
2
Check of IGBT circuit
P2 - L1 , P2 - L2 , P2 - L3 , N2 - L1 , N2 - L2 , N2 - L3
3
Check of INVERTER circuit
P3 - U , P3 - V , P3 - W , N3 - U , N3 - V , N3 - W
Note: The marks R , S , L1 , L2 , L3 , P1 , P2 , P3 , N1 , N2 , N3 , U , V and W
shown in the diagram are not actually printed on the board.
P1
N1
R
S
N2
P3
U
V
W
N3
L3
P2
L1
L2
CNAC1, CNAC2
230 V AC
Connect to the outdoor
controller circuit board
(CNAC)
EI, E2, E3, E4
Connect to the earth
CN2
Connect to the outdoor
controller circuit board (CN2)
1
-
5
:Transmitting signal to
outdoor controller
circuit board (0-5 V DC)
2
-
5
: Zero cross signal
(0-5 V DC)
3
-
4
:16 V DC
6
-
5
:16 V DC
7
-
5
:16 V DC
CN4
Connect to the outdoor
controller circuit board
(CN4)
NI, LI
Voltage of 230
V AC is input
(Connect to the
terminal block
(TB1))
CNDC
280-380 V DC (
1
+,
3
-)
Connect to the out-
door controller circuit
board (CNDC)
CN6
Thermistor
TB1A, TB2A, TB3A,
TB1B, TB2B, TB3B
Connect to DCL
PUHZ-SP125VKA.TH
PUHZ-SP140VKA.TH