76
Floor
standing
PSA-KA
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
Function
Settings
No.
Mode
No.
Setting
: Initial setting (Factory setting)
- : Not available
4-Way
cassette
Ceiling
suspended
Wall mounted
PLA-BA
Filter sign
100h
1
2500h
07
2
No filter sign indicator
3
Air flow
Quiet
1
(Fan speed)
Standard
08
2
High ceiling
3
No.of air outlets
4 directions
1
3 directions
09
2
2 directions
3
Optional high efficiency Not supported
10
1
filter
Supported
2
Vane setting
No vanes (Vane No.3 setting : PLA only)
1
Vane No.1 setting
11
2
Vane No.2 setting
3
Optional humidifier
Not supported
13
1
(PLA only)
Supported
2
Vane differential setting No.1 setting (TH5: 24–28°C)
1
in heating mode
No.2 setting (Standard, TH5:28–32°C) 14 2
(cold wind prevention)
No.3 setting (TH5: 32–38°C)
3
Swing
Not available Swing
23
1
Available Wave air flow
2
Set temperature in heating Available
24
1
mode (4 deg up) *
* PKA-HAL/KAL: 2 deg up
Not available
2
Fan speed during the
Extra low
1
heating thermo OFF
Stop
25
2
Set fan speed
3
Fan speed during the
Set fan speed
27
1
cooling thermo OFF
Stop
2
Detection of abnormality of Available
28
1
the pipe temperature (P8) Not available
2
}
PLA-BA
PKA-HAL PKA-KAL
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
PSA-KA
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
PCA-KAQ
—
—
—
—
—
Ceiling
concealed
PEA-GA
—
—
—
—
—
—
—
—
—
—
—
—
(2) Functions available when setting the unit number to 01–03 or AL (07 in case of wireless remote controller)
• When setting functions for an indoor unit in an independent system, set the unit number to 01 referring to
4
setting the
indoor unit number of Operating Procedure.
• When setting functions for a simultaneous- Twin Triple indoor unit system, set the unit number to 01 to 03 for each indoor
unit in case of selecting different functions for each unit referring to
4
setting the indoor unit number of Operating Procedure.
• When setting the same functions for an entire simultaneous Twin Triple-indoor unit system, set refrigerant address to AL (07
in case of wireless remote controller) referring to
4
setting the indoor unit number of Operating Procedure.
PEAD-RP
•
JA(L)Q
Function
Settings
No.
Mode
No.
Setting : Initial setting
(Factory setting)
Filter sign
100h
1
2500h
07
2
No filter sign indicator
3
External static pressure 35/50/70/100/150Pa
08
10
1
2
Extra low
3
Fan speed during the
heating thermo OFF
Stop
25
1
Set fan speed
2
27
1
2
Detection of abnormality
of the pipe
1
28
2
Set temperature in heating
24
mode (4 deg up)
Refer to the right table
External static pressure 35/50/70/100/150Pa
Refer to the right table
Available
Not available
Fan speed during the
cooling thermo OFF
Set fan speed
Stop
Available
Not available
External static
pressure
Setting No.
Initial setting
(Factory setting)
35Pa
50Pa
70Pa
100Pa
150Pa
2
3
1
2
3
Mode No. 08 Mode No. 10
1
1
2
2
2
Mode No.11
Setting No.
Settings
PLA-BA
PCA-KAQ
1
No Vanes
Vane No.3 setting
( Downward position than the standard )
Less smudging
No vane function
2
Vane No.1 setting
Standard
Standard
3
Vane No.2 setting
Less draft * (Upward position than the standard) Less draft * (Upward position than the standard)
* Be careful of the smudge on ceiling.
OCH582B
Summary of Contents for PUHZ-P200YKA.UK
Page 101: ...101 OCH582B ...