Parts name
Check points
Disconnect the connector then measure the resistance with a tester.
(At the ambient temperature 10
:
~30
:
)
Thermistor (TH3)
<Outdoor pipe>
Thermistor (TH4)
<Discharge>
Thermistor (TH6)
<Outdoor 2-phase pipe>
Thermistor (TH7)
<Outdoor>
Thermistor (TH8)
<Heatsink>
Normal
160k
"
~410k
"
4.3k
"
~9.6k
"
39k
"
~105k
"
TH4
TH3
TH6
TH7
TH8
Abnormal
Open or short
Measure the resistance between the terminals with a tester.
(At the ambient temperature 20
:
)
Solenoid valve coil
<Four-way valve>
(21S4)
Motor for compressor
(MC)
Linear expansion valve
(LEV-A)
Normal
Abnormal
Open or short
P100, P125/140VHA2
1
P125/P140VHA2
Disconnect the connector then measure the resistance with a tester.
(Winding temperature 20
:
)
Normal
Gray - Black
Gray - Red
Gray - Yellow
Gray - Orange
Abnormal
46
±
3
"
Open or short
Measure the resistance between the terminals with a tester.
(At the ambient temperature 20
:
)
Normal
1450
±
150
"
Abnormal
Open or short
Solenoid valve coil
<Bypass valve>
(SV)
For P125, 140
Refer to next page.
Fan motor(MF1,MF2)
1500
±
150
"
1435
±
150
"
P125,P140
P100
0.88
"
0.53
"
Measure the resistance between the terminals with a tester.
(Winding temperature 20
:
)
Normal
Abnormal
Open or short
W
V
U
11-6. HOW TO CHECK THE PARTS