10 to 16 V DC?
Y ES
NO
Lighting
B linking
Lighting
B linking
Check the voltage of the
terminal block (TB 6) of
the remote controller.
Check the status of the LED2
after disconnecting the remote
controller wire from the terminal
block (TB 5) of the indoor unit.
remote controller
remote controller.
contact of the remote
controller wire
remote controller wire.
Check the voltage of the
terminal block (TB 5)
connecting the remote
controller wire.
If it is not between DC 10V
and DC16V , the indoor
controller board must be
defective.
wire short-circuits
controller wire is
short-circuited.
controller board
controller board.
Diagnosis flow
Cause
troubleshooting
S y mp toms: N oth ing is disp lay ed on th e remote c ontroller.
3
controller board
LED1 :
LED2 : or
LED3 : —
Check the status
of the LED2.
Check the status
of the LED2.
OCH526C
Summary of Contents for PUHZ-HW112YHA-BS
Page 124: ...C ...