C
F
B
C
F
<A> Make sure the pipes from the twinning pipe to the outdoor unit are
sloped downwards (towards the twinning pipes).
F
C
2m
F
D
E
C
<B> When the piping on the outdoor unit side (from the twinning pipe)
exceeds 2 m, ensure a trap (gas pipe only) within 2 m.
<C> Slope of twinning pipes
15±
F
G
<D> Pipe connection example [EP650]
A
: Downward slope
B
: Upward slope
C
: Indoor unit
D
: Trap (gas pipe only)
E
: Within 2 m
F
: Twinning pipe
G
: Slope of the twinning pipe is at an angle within ±15° to the ground
H
: Pipes on site
I
: Twinning kit
J
: Straight run of pipe that is 500 mm or more
6
: ODø12.7
×
IDø9.52 (Included with outdoor unit)
8
: ODø19.05
×
IDø15.88 (Included with outdoor unit)
c
: ODø34.93
×
IDø28.58 (Included with outdoor unit)
(
6
,
8
,
c
: Refer to item 10.2)
H
H
J
J
H
I
6
I
c
8